Product Details:
Payment & Shipping Terms:
|
Manufacturer: | Pepperl+Fuchs | Product Type: | SMART Current Driver |
---|---|---|---|
Product No: | HiC2031 | Signal Type: | Analog Output |
Ripple: | ≤ 10 % | Rated Current: | ≤ 30 MA At 24 V |
Leading Time: | Negotiable | Shipping Weight: | 1 Kg |
High Light: | Analog Output HiC2031,SMART Current Driver HiC2031,PEPPERL FUCHS HiC2031 |
Manufacturer : Pepperl+Fuchs
Product No :HiC2031
Product Type : SMART Current Driver
Signal type : Analog output
Supply Connection : SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage Un : 19 ... 30 V DC via Termination Board
Ripple : = 10 %
Power dissipation : = 600 mW
Power consumption : = 700 mW
Input/Output : safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Ambient temperature : -20 ... 60 °C (-4 ... 140 °F)
Degree of protection : IP20
Mounting : Termination Board
Dimensions ( L x W x H ) : 1.2cm x 12.8cm x 10.6cm
Weight : Approx. 0.1 Kg
Shipping Weight : 1.5 Kg
This isolated barrier is used for intrinsic safety applications. It repeats the input signal from a control system to drive HART I/P converters, valve actuators, and displays located in a hazardous area. Digital signals are superimposed on the analog values at the field side or control side and are transferred bi-directionally.
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Systematic capability (SC) | SC 3 | |
Supply | ||
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) | |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board | |
Ripple | ≤ 10 % | |
Rated current | ≤ 30 mA at 24 V | |
Power dissipation | ≤ 600 mW at 20 mA and 500 Ω load | |
Power consumption | ≤ 700 mW | |
Input | ||
Connection side | control side | |
Connection | SL1: 8a(+), 7a(-) | |
Input signal | 4 ... 20 mA , limited to approx. 26 mA | |
Input voltage | open loop voltage of the control system < 30 V | |
Voltage drop | approx. 6 V at 20 mA | |
Input resistance | > 100 kΩ, with field wiring open | |
Output | ||
Connection side | field side | |
Connection | SL2: 5a(+), 5b(-) | |
Voltage | ≥ 13 V at 20 mA | |
Current | 4 ... 20 mA | |
Load | 0 ... 650 Ω | |
Ripple | 20 mV rms | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis |
|
Influence of ambient temperature | < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) | |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB) |
|
Rise time | 10 to 90 % ≤ 10 ms | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff | |
Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 For further information see system description. |
|
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | UL 61010-1:2012 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D) | |
Mounting | on termination board | |
Coding | pin 1 and 3 trimmed For further information see system description. |
|
Data for application in connection with hazardous areas | ||
EU-type examination certificate | CESI 06 ATEX 017 | |
Marking | ![]() ![]() ![]() |
|
Output | Ex ia | |
Supply | ||
Maximum safe voltage | 250 V AC (Attention! Um is no rated voltage.) | |
Equipment | SL2: 5a(+), 5b(-) | |
Voltage | 25.2 V | |
Current | 100 mA | |
Power | 630 mW | |
Internal capacitance | 5.7 nF | |
Internal inductance | negligible | |
Certificate | CESI 19 ATEX 027 X | |
Marking | ![]() |
|
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015 | |
International approvals | ||
FM approval | ||
FM certificate | FM 19 US 0122 X , FM 19 CA 0065 X | |
Control drawing | 116-0470 (cFMus) | |
UL approval | E106378 | |
Control drawing | 116-0458 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx CES 06.0002X | |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
· 1-channel isolated barrier
· 24 V DC supply (bus powered)
· Current output up to 650 Ω load
· Low power dissipation
· Up to SIL 2 acc. to IEC 61508
Best possible prices and delivery time
Long time experience in the field
Well trained staff
Own warehouse facilities
Best relationships with branch office of manufacture
Flexible and individual service for you
Cheap and safe forwarder for shipments (air)
Q: Does your goods are new and original?
A: Yes, they are new and original.
Q: How long warranty?
A: One-year warranty.
Q: Does any certificates can be provided?
A: Yes, it depends on what product you request, please check details with you
Contact Person: Mrs. Joanna Yang
Tel: +86-13828861501
Fax: 86-755-26850713