Product Details:
Payment & Shipping Terms:
|
Manufacturer: | Pepperl+Fuchs | Product No: | KFD2-SH-Ex1.T.OP |
---|---|---|---|
Product Type: | Switch Amplifier | Voltage: | 9.56 V |
Ripple: | ≤ 10 % | Mass: | Approx. 150 G |
Leading Time: | Negotiable | Shipping Weight: | 1 Kg |
High Light: | IP20 PEPPERL FUCHS Switch Amplifier,KFD2-SH-Ex1.T.OP,Isolated Switch Amplifiers P&f |
Manufacturer : Pepperl+Fuchs
Product No. : KFD2-SH-Ex1.T
Product type : Switch Amplifier
Signal type : Digital Input
Connection : Terminals 14, 15
Rated voltage : 20 ... 30 V DC
Ambient temperature : -20 ... 60 °C (-4 ... 140 °F)
Degree of protection : IP20
24 V DC
1-channel isolated barrier
24 V DC supply
Input for approved dry contacts or SN/S1N sensors
Active voltage output
Relay contact output
Fault indication output
Line fault detection (LFD)
Shipping weight : 2.5 Kg
This isolated barrier is used for intrinsic safety applications.
The device transfers digital signals (SN/S1N proximity sensors or approved dry contacts) from a hazardous area to a safe area.
The input controls one active voltage output and one relay contact output with a NO contact. Unlike an SN/S1N series proximity sensor, a mechanical contact requires a 10 kΩ resistor to be placed across the contact in addition to a 1.5 kΩ resistor in series.
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Performance level (PL) | PL d | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 100 mA | |
Power dissipation | 1.5 W | |
Power consumption | max. 1.7 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4+, 6- | |
Open circuit voltage/short-circuit current | approx. 8.4 V DC / approx. 11.7 mA | |
Lead resistance | max. 50 Ω , cable capacitances and inductances must be observed in hazardous areas | |
Switching point | ||
Relay de-energized | I < 2.1 mA and I > 5.9 mA , output switched off | |
Relay energized | 2.8 mA < I < 5.3 mA , output switched on | |
Response delay | ≤ 1 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7+, 8- ; output II: terminals 9, 10 ; output III: terminals 11, 12 | |
Output I | active voltage output, short-circuit proof 0-signal: 0 V 1-signal: 19 V DC at 15 mA ... 31 V DC at no-load fault: 0 V |
|
Output II | relay | |
Contact loading | 48 V AC/DC 250 mA |
|
Mechanical life | ≤ 20 x 106 switching cycles | |
Output III | relay , fault signal | |
Contact loading | 48 V AC/DC 250 mA |
|
Mechanical life | ≤ 20 x 106 switching cycles | |
Transfer characteristics | ||
Switching frequency | ||
Output I | ≤ 50 Hz | |
Output II | ≤ 5 Hz | |
Output III | ≤ 5 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Machinery Directive | ||
Directive 2006/42/EC | EN/ISO 13849-1:2015 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Safety | IEC/EN 61508:2010 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 00 ATEX 2041 | |
Marking | ![]() |
|
Input | Ex ia IIC | |
Voltage | 9.56 V | |
Current | 16.8 mA | |
Power | 41 mW (linear characteristic) | |
Supply | ||
Maximum safe voltage | 40 V AC/DC (Attention! The rated voltage can be lower.) | |
Output | ||
Contact loading | 48 V AC/DC 250 mA |
|
Maximum safe voltage | 60 V AC/DC (Attention! The rated voltage can be lower.) | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | ![]() |
|
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 | |
International approvals | ||
IECEx approval | ||
IECEx certificate | IECEx PTB 21.0010 IECEx TUN 19.0013X |
|
IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC Ex ec nC IIC T4 Gc |
· 1-channel isolated barrier
· 24 V DC supply (Power Rail)
· Input for approved dry contacts or SN/S1N sensors
· Active voltage output
· Relay contact output
· Fault indication output
· Line fault detection (LFD)
· Up to SIL 3 acc. to IEC/EN 61508
· Up to PL d acc. to EN/ISO 13849
Best possible prices and delivery time
Long time experience in the field
Well trained staff
Own warehouse facilities
Best relationships with branch office of manufacture
Flexible and individual service for you
Cheap and safe forwarder for shipments (air)
Q: Does your goods are new and original?
A: Yes, they are new and original.
Q: How long warranty?
A: One-year warranty.
Q: Does any certificates can be provided?
A: Yes, it depends on what product you request, please check details with us.
Contact Person: Frank
Tel: +8613823172318