Send Message
Great System International Limited

Great System International Limited

Home ProductsPEPPERL FUCHS Safety Barrier

IP20 Pepperl Fuchs KFA6-SR2-Ex2.W Switch Amplifier

Certification
China Great System International Limited certification
Hello Qiang. Happy New 2021 Year! We start working Year from today. Thank you very much for cooperation in the last year and hope we will do it better this year!

—— Alexandr Blagov

Frank, Thank you for your honesty and your company trusty last year I hope will be extend our business together next year.Have a good holiday.

—— Hbabaee

It has been very nice to cooperate with you through all these years and thank you so much for your kind support and best service!

—— Niloufar Soltani

I'm Online Chat Now

IP20 Pepperl Fuchs KFA6-SR2-Ex2.W Switch Amplifier

IP20 Pepperl Fuchs KFA6-SR2-Ex2.W Switch Amplifier
IP20 Pepperl Fuchs KFA6-SR2-Ex2.W Switch Amplifier IP20 Pepperl Fuchs KFA6-SR2-Ex2.W Switch Amplifier

Large Image :  IP20 Pepperl Fuchs KFA6-SR2-Ex2.W Switch Amplifier

Product Details:
Place of Origin: Singapore
Brand Name: Pepperl + Fuchs
Certification: ROHS
Model Number: KFA6-SR2-Ex2.W
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: Negotiable
Packaging Details: carton
Delivery Time: 4-6 days
Payment Terms: T/T
Supply Ability: 100+pc+on stock
Detailed Product Description
Signal Type: Digital Input Connection: Terminals 14, 15
Rated Voltage: 207 ... 253 V AC, 45 ... 65 Hz Power Loss: 1.2 W
Power Consumption: ≤ 1.3 W Degree Of Protection: IP20
Mass: Approx. 150 G Dimensions: 20 X 119 X 115 Mm
High Light:

KFA6-SR2-Ex2.W Switch Amplifier

,

IP20 Switch Amplifier

,

KFA6-SR2-Ex2.W Pepperl Fuchs Switch Amplifier

P+F KFA6-SR2-Ex2.W Switch Amplifier

 

 

General specifications
Signal type Digital Input
Supply
Connection terminals 14, 15
Rated voltage 207 ... 253 V AC, 45 ... 65 Hz
Power loss 1.2 W
Power consumption ≤ 1.3 W

 

Input
Connection terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio ≥ 20 ms / ≥ 20 ms

 

Output
Connection output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, II signal ; relay
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Mechanical life 107 switching cycles

 

Transfer characteristics
Switching frequency ≤ 10 Hz
Electrical isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Directive conformity

 

Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Low voltage
Directive 2006/95/EC EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

 

Data for application in connection
with Ex-areas
EC-Type Examination Certificate PTB 00 ATEX 2081 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection ¬ II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC
Input [Ex ia] IIC, [Ex ia] IIIC
Voltage Uo 10.6 V
Current Io 19.1 mA
Power Po 51 mW (linear characteristic)
Supply
Maximum safe voltage Um 253 V AC (Attention! Um is no rated voltage.)

 

Output
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Maximum safe voltage Um 253 V AC (Attention! The rated voltage can be lower.)
Electrical isolation
Input/input not available
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2009, EN 60079-11:2007 , EN 61241-11:2006
International approvals
FM approval
Control drawing 116-0035

 

IP20 Pepperl Fuchs KFA6-SR2-Ex2.W Switch Amplifier 0IP20 Pepperl Fuchs KFA6-SR2-Ex2.W Switch Amplifier 1

Contact Details
Great System International Limited

Contact Person: Mrs. Joanna Yang

Tel: +86-13828861501

Fax: 86-755-26850713

Send your inquiry directly to us (0 / 3000)