logo
About Us
China GREAT SYSTEM INDUSTRY CO. LTD
About Us
GREAT SYSTEM INDUSTRY CO. LTD
Great System Industry (GSI) is a premier provider of process control instrumentation and industrial automation sensors, headquartered in Hong Kong with operations since 1998. As an ISO-certified manufacturer, distributor, and trading company, GSI delivers high-precision measurement solutions—including pressure, temperature, flow, and level sensors—to over 6,000 customers worldwide. With an export ratio of 80%-90% and annual sales reaching $7-10 million, we serve diverse industries across Europe, ...
Read more
Request A Quote
0+
Annualsales
0
Year
Customers
0%
P.C
0+
Employees
WE PROVIDE
THE BEST SERVICE!
You can contact us in various ways
Contact Us
GREAT SYSTEM INDUSTRY CO. LTD

Quality GE Bently Nevada & E&H Instrument factory

Events
Lastest company news about Three-Valve Manifold Operation for DP Transmitters: Correct Commissioning and Shutdown Steps
Three-Valve Manifold Operation for DP Transmitters: Correct Commissioning and Shutdown Steps

2026-10-14

Three-Valve Manifold Operation for Differential Pressure Transmitters: Getting Commissioning and Shutdown Right Whether a differential pressure (DP) transmitter delivers an accurate flow, level, or differential pressure reading depends half on the transmitter itself and half on how the three-valve manifold is operated. The manifold looks like nothing more than a metal block with three handles, but turning those handles in the wrong order can at best distort your data and at worst destroy the transmitter's diaphragm capsule. This article explains the correct commissioning and shutdown procedures, and the principles behind them. What Are the Three Valves? The three-valve manifold is mounted between the high- and low-pressure ports of the DP transmitter and contains three manual valves: High-pressure (HP) valve: connects the transmitter's high-pressure chamber to the upstream impulse line. Low-pressure (LP) valve: connects the low-pressure chamber to the downstream impulse line. Equalizing (balance) valve: connects the high- and low-pressure chambers; closed before commissioning, opened during shutdown. Working together, their core task is to keep the two sides of the diaphragm capsule balanced and controllable at all times, so it never experiences a one-sided pressure shock. Commissioning: Open in Sequence — Don't Skip Steps After a DP transmitter is installed, with impulse lines connected but no process fluid admitted yet, all three valves are normally closed. Commissioning follows this order: Open the HP valve. High-pressure fluid enters the impulse line. The equalizing valve is still open, so HP fluid passes through it into the LP chamber too, keeping both sides equal and the capsule free from one-sided shock. Close the equalizing valve. Once the HP impulse line is full, close the equalizing valve to cut the bypass between the two chambers. Open the LP valve. Finally open the LP valve, admitting low-pressure fluid to the LP chamber. Both sides now see their true process pressures and the transmitter outputs the real differential pressure. Commissioning rule: open HP → close equalizer → open LP. The order must never be reversed — and never close the equalizing valve before opening a single-side valve. Shutdown: Reverse the Order, With Different Details Close the LP valve. Cut off the low-pressure side first; the HP side is still working while the equalizer remains closed. Open the equalizing valve. HP fluid now flows through the equalizer into the LP chamber, rebalancing both sides. Close the HP valve. Finally cut off the high-pressure side so the manifold is fully closed and the transmitter can be safely removed or serviced. Shutdown rule: close LP → open equalizer → close HP. The timing of the equalizing valve is critical — it must be opened before the HP valve is closed. Two Red Lines You Must Never Cross Never subject the DP capsule to one-sided pressure. The measuring capsule is designed for differential pressure, not full process pressure on one side; opening only one take-off valve with the equalizer closed pushes the capsule to one side, causing drift or permanent deformation. Never let condensate or fill fluid escape from impulse lines or seal pots. Many DP systems rely on condensate in the impulse line or fill fluid in a seal pot to transmit pressure. Draining a line or losing fill fluid destroys the measurement — especially in steam flow service, where the impulse lines must be full of condensate before commissioning. Common Mistakes and Their Consequences MistakeConsequence Closing the equalizer before opening the HP or LP valveOne-sided pressure on the capsule; output spikes, zero drift, or capsule damage Closing the HP valve on shutdown without opening the equalizer firstLP side stays connected to the process; capsule suffers reverse one-sided pressure Commissioning before impulse lines fill with condensate (steam service)Steam reaches the transmitter directly; readings fluctuate and the capsule may overheat Opening or closing valves too quicklyPressure surge saturates the output; water-hammer shock on the capsule These errors rarely cause immediate failure. A single one-sided pressure event may not damage the capsule, but after several times the elastic element's stress characteristics change, showing up as zero drift and worse linearity — eventually misdiagnosed as transmitter aging and replaced, when the real problem was the operation. Conclusion The steps are simple; doing them by the book every time is the hard part. Remember: commission with "open HP, close equalizer, open LP," and shut down with "close LP, open equalizer, close HP." For steam service, add one rule: if the condensate is not full, do not touch the manifold.
View More
Lastest company news about Emerson TREX2 Power-the-Loop: Boost Field Commissioning Efficiency for New Construction Projects
Emerson TREX2 Power-the-Loop: Boost Field Commissioning Efficiency for New Construction Projects

2026-10-14

Emerson TREX2 "Power-the-Loop": The Smart Way to Commission Instruments on New Projects During the startup and commissioning phase of a new construction project, instrument technicians face a familiar frustration: the instruments are on site, but the control loop is not yet powered. The DCS cabinet is not energized, the marshalling wiring is incomplete, and a handheld communicator cannot read the device because there is no loop power. What if the communicator itself could supply that power? That is exactly what the Power-the-Loop function of the Emerson TREX2 field communicator delivers. What Is the TREX2 Power-the-Loop Function? The TREX2 is Emerson's second-generation smart field communicator, supporting both HART and FOUNDATION Fieldbus (FF) protocols. Power-the-Loop is a core capability of the L-Plus (enhanced communication) module: the communicator contains a built-in 24V DC power module that can directly power two-wire HART transmitters or FF bus devices, with no external loop power supply required. Which Models Support Power-the-Loop? Model recognition tip: TREX2 models containing the letter "L" (such as TREXLFPKLWS3S) generally include the L-Plus module, while models with "C" (such as TREXCHPNAWS1) use the standard module. Choosing the right module matters when offline powering is a daily requirement. How It Works A two-wire HART transmitter uses the loop current both to transmit the 4-20mA analog signal and to power itself. Normally this power comes from a DCS AI card or a separate power distribution cabinet. Power-the-Loop simply lets the TREX2 play that role temporarily: it outputs 24V DC on the HART+pwr terminal and includes a built-in 250Ω load resistor, satisfying the loop impedance required by HART digital communication (230Ω-600Ω, with 250Ω being optimal). Three On-Site Pain Points It Solves No power available on new projects: instead of carrying an external 24V supply plus a 250Ω resistor with complex wiring, a single communication cable connects the communicator directly to the transmitter with automatic power and communication. Offline calibration in the workshop: power, communication, current measurement, and loop diagnostics in one device — cutting the number of tools carried by more than 50%. Separating instrument faults from wiring faults: with the loop isolated, technicians can measure loop voltage, current, and impedance, and identify shorts, opens, and poor contacts to determine whether the instrument or the wiring is at fault. Efficiency Tips for New Project Commissioning TechniqueMethodEfficiency Gain Offline pre-configurationConfigure LRV/URV, engineering units, damping, Tag and output mode as soon as instruments arriveOver 50% shorter on-site commissioning Batch valve positioner setupGuided Setup for actuator type, auto travel calibration, air supply, control mode, and step response testingFrom 30 minutes to under 10 minutes per unit (3x) Loop integrity pre-verificationVerify cable continuity, terminal contact, and total loop impedance before DCS power-upOver 60% less fault-clearing time Bluetooth remote commissioningOperate via a phone/tablet app from a safe area for hazardous locationsOne person does the work of two Key Precautions on Site Disconnect the device from the system loop before using Power-the-Loop, to avoid conflicts between TREX2 and DCS power. The 250Ω resistor trap: a normal 4-20mA signal does not guarantee reliable HART communication; the 230Ω-600Ω loop impedance must be satisfied. Do not power: four-wire instruments, WirelessHART devices, or any device already connected to an external power source. Selection Advice: Does Your Project Need It? Power-the-Loop is strongly recommended for new project startups, frequent offline bench calibration, sites without a 24V supply, and fast loop diagnostics. It is less critical for teams doing mainly online maintenance with a permanent DCS supply. Conclusion TREX2's Power-the-Loop essentially integrates "external power supply + load resistor + multimeter" into the communicator itself. For new project commissioning, its core value is clear: pre-configure before the system is energized, carry fewer tools, diagnose offline, and roughly double commissioning efficiency. On an industrial site where every minute is money, that is a worthwhile investment.
View More
Lastest company news about Generator Gas Replacement During Startup and Shutdown: Full Procedure and Key Safety Precautions
Generator Gas Replacement During Startup and Shutdown: Full Procedure and Key Safety Precautions

2026-10-09

Generator Gas Replacement During Startup and Shutdown: Full Procedure and Safety Precautions Generator gas replacement must be carried out only after the generator has passed its air-tightness test and its insulation is qualified. The replacement can be performed while the rotor is stationary or running on the turning gear. This article walks through pre-checks, precautions, the startup and shutdown replacement processes, and routine hydrogen makeup. 1. Pre-Replacement Checks Put the turbine lube oil system and seal oil system into service. Carry out a full inspection of the hydrogen system to confirm replacement conditions are met. Before replacement, stop the circulating fan and isolate the online humidity meter and purity meter. Tools: power reel, copper wrench, copper hook (never use iron wrenches or hooks), and lamps (for baking piping and valves when using CO2). 2. Key Precautions During Replacement No hot work is allowed in the surrounding area during gas replacement. Copper wrenches and hooks must be used — iron tools are forbidden to avoid sparks. When working around the hydrogen system, the site must be well ventilated and well lit. Closely watch that the oil-hydrogen differential pressure tracks automatically and correctly; if not, adjust manually. 3. Startup Gas Replacement Step 1 — Replace air with CO2: Connect the CO2 cylinder outlet to the manifold interface. Open the generator CO2 inlet valve. Slowly open the CO2 discharge valve and let CO2 enter the generator, carefully controlling the charging rate. Maintain the generator internal gas pressure at 0.02–0.03 MPa during replacement. Repeatedly purge the dead corners, sampling valves and oil-water detector drains. When CO2 purity reaches ≥ 85%, purity is qualified and CO2 replacement is complete. Step 2 — Replace CO2 with hydrogen: Drain the CO2 from the generator. Contact the hydrogen plant operator and confirm the makeup method. Maintain the generator internal gas pressure at 0.02–0.03 MPa during replacement. Control the hydrogen charging rate to prevent a hot spot from excessive hydrogen velocity at pipe reducers, which could cause an accident. Repeatedly purge the dead corners, sampling valves and oil-water drains. When hydrogen purity reaches ≥ 96%, purity is qualified and hydrogen replacement is complete. Put the hydrogen dryer, circulating fan, purity meter, humidity meter and generator insulation device into service. 4. Shutdown Gas Replacement First replace the generator hydrogen with CO2; purity ≥ 95% is qualified. Then replace the generator CO2 with air; purity reaching 15% is qualified. The shutdown process is similar to startup — only the required purity differs at each stage. 5. Hydrogen Makeup During Operation Open the hydrogen makeup valve. Contact the hydrogen plant for makeup. Adjust the makeup pressure. When hydrogen pressure is sufficient, contact the hydrogen plant to stop makeup; after the makeup pressure drops, close the makeup valve. Control the makeup rate throughout the process. 6. Summary of Key Points PointRequirement Online metersIsolate the online purity meter and humidity meter for both startup and shutdown replacement. SafetyNo hot work at all times; ensure ventilation; use copper tools only. Differential pressureEnsure oil-hydrogen differential pressure tracks automatically; adjust promptly if not. Speed controlControl the charging and exhausting speed during replacement. PurityPurity must always meet the values specified in the operating procedures.
View More
Lastest company news about Deaerator Pressure and Temperature Changes: Why They Affect Dissolved Oxygen in Boiler Feedwater Systems
Deaerator Pressure and Temperature Changes: Why They Affect Dissolved Oxygen in Boiler Feedwater Systems

2026-10-09

Deaerator Pressure and Temperature Changes: Why They Affect Dissolved Oxygen During normal operation of a turbine unit, dissolved oxygen in boiler feedwater always fluctuates whenever the deaerator pressure or temperature rises or falls. But do you really understand how dissolved oxygen changes, and why? This article explains the mechanics behind these fluctuations and how to keep dissolved oxygen within the qualified range. The Core Principle Behind Deaeration First, it is essential to understand the core of deaeration: only by heating the water to the saturation temperature that corresponds to the current pressure can the dissolved gases inside the water be released. Pressure and saturation temperature have a one-to-one correspondence. However, the change of water temperature always lags behind the change of pressure, and this lag is the root cause of dissolved oxygen fluctuation in the deaerator. Case 1: When Deaerator Pressure Suddenly Rises When the deaerator pressure rises, the water temperature does not rise in sync. At this moment, the water temperature is lower than the saturation temperature at the current pressure. Because the water has not reached its saturation temperature, deaeration performance deteriorates, and the dissolved oxygen in the water rises. Immediate effect: Water temperature lags below saturation temperature → deaeration weakens → dissolved oxygen increases. After a period of time: Once the deaerator heats the water up to the saturation temperature at the new pressure, dissolved oxygen falls again and returns to the qualified range. Case 2: When Deaerator Pressure Suddenly Drops When the deaerator pressure drops, the water temperature decreases slowly. At this moment, the water temperature is higher than the saturation temperature at the current pressure, so the water is in an “oversaturated” state. In this state, the dissolved gases in the water are more easily released, and the dissolved oxygen decreases. Immediate effect: Water temperature lags above saturation temperature → gas readily escapes → dissolved oxygen drops temporarily. After a period of time: Once the water temperature gradually falls and matches the saturation temperature of the new pressure, deaeration capacity returns to normal and dissolved oxygen slowly climbs back. Summary of Pressure Change Effects on Dissolved Oxygen Pressure ChangeWater Temperature BehaviorWater StateDissolved Oxygen Trend Pressure suddenly risesLags below saturation temperatureUnder-saturatedIncreases, then falls back to normal Pressure suddenly dropsLags above saturation temperatureOversaturatedDecreases temporarily, then climbs back Conclusion In short: when deaerator pressure rises sharply, the water temperature lags below the saturation temperature, so dissolved oxygen increases; when pressure drops sharply, the water temperature lags above the saturation temperature, gases are easily released, and dissolved oxygen temporarily decreases. Understanding this lag relationship helps operators anticipate dissolved oxygen fluctuation before it exceeds the qualified range, ensuring stable and reliable deaeration performance in boiler feedwater systems.
View More
Lastest company news about How Long Should the Straight Pipe Sections Be Before and After an Electromagnetic Flow Meter?
How Long Should the Straight Pipe Sections Be Before and After an Electromagnetic Flow Meter?

2026-09-21

When installing an electromagnetic flow meter, one of the most common questions on site is how long the straight pipe sections before and after the meter should be. The flow profile inside the pipe directly affects measurement accuracy, so getting these lengths right matters. The Basic Rule: 5D Upstream and 2D Downstream As a starting reference, use an upstream straight section of at least 5D and a downstream section of at least 2D, where D is the nominal pipe diameter. For a DN100 meter, that means keeping at least 500 mm upstream and 200 mm downstream. These values are a practical layout guide, and the actual requirement depends on the fittings installed ahead of the meter. Why the Upstream Section Must Be Longer An electromagnetic flow meter calculates flow rate from the induced voltage generated as a conductive liquid passes through a magnetic field. After the liquid passes an elbow, tee, valve, or reducer, the velocity distribution is distorted and may swirl. If the meter is too close to these fittings, the flow has not stabilized when it enters the measuring tube, and the reading is affected. The upstream straight section gives the disturbed flow time to recover. Because the fluid entering the meter comes directly from the upstream side, the upstream section is normally longer than the downstream one. How Fittings Affect the Required Length FittingRecommendation Simple straight pipe (no disturbing fittings nearby)Upstream ≥5D, downstream ≥2D Single 90° elbowKeep the upstream straight length as long as possible Two consecutive elbows (especially out of plane)Lengthen the upstream section; swirl is stronger TeeIncrease the distance to give the flow room to recover Control valveBest layout: upstream pipe → flow meter → control valve, placing the valve after the meter Pump outletKeep a full upstream section, ensure the pipe runs full, and avoid air entrainment or cavitation What Counts as an Effective Straight Pipe Section A straight pipe section is not just about the pipe being physically straight. Within this length there should be no elbows, tees, valves, obvious reducers, or deeply inserted parts such as temperature sleeves or sampling tubes, and the diameter must stay consistent without sudden changes in cross-section. A pipe that measures 5D but contains a deep thermowell still disturbs the flow, so do not rely on length alone — check what is inside the pipe. When Space Is Limited In retrofit projects the piping is already built and space is tight. In that case: check the meter's manual for the specific straight-section requirement; see whether elbows, tees, or valves can be moved; check whether the meter position can be adjusted; and, if space is truly limited, select a model designed for shorter straight sections. Do not judge only by whether the meter physically fits — make sure the measurement conditions are adequate. Summary For an electromagnetic flow meter, start with upstream ≥5D and downstream ≥2D. If elbows, tees, control valves, pump outlets, or reducers are present upstream, lengthen the straight sections accordingly, and always confirm the final requirement against the specific model's manual. Check three things: what fittings are ahead of the meter, whether the straight section is truly clean, and what the manual requires. If you need help selecting the right electromagnetic flow meter or confirming installation requirements, please contact us for professional advice and a tailored quotation.
View More
Latest company case about Condenser and Deaerator Dissolved Oxygen Exceedance: Causes, Hazards and Corrective Actions
Condenser and Deaerator Dissolved Oxygen Exceedance: Causes, Hazards and Corrective Actions

2026-10-09

Condenser and Deaerator Dissolved Oxygen Exceedance: Causes and Corrective Actions Dissolved oxygen refers to the oxygen dissolved in water, measured in µg/L. During operation, if the oxygen content in condensate or feedwater exceeds the value specified in the operating procedures, it is considered dissolved oxygen exceedance. The dissolved oxygen in the condenser and deaerator must be kept within limits; once it exceeds them, adjustment should be made immediately. Hazards of Dissolved Oxygen Exceedance Oxygen causes oxidation corrosion of metal equipment such as pipes, valves, feedwater pumps, high- and low-pressure heaters, economizers and water walls, producing rust and impurities. Impurities clog filters and valves, affecting feedwater flow. Impurities deposit on heating surfaces, causing scaling, reducing heat-exchange efficiency and potentially leading to tube-wall bursting. Consumption of deoxygenation chemicals increases, raising unit operating costs. Long-term exceedance seriously threatens the safe and stable operation of the unit. Causes and Treatment: Condenser Dissolved Oxygen Exceedance Check whether outside air leaks into the condenser — inspect condenser vacuum, shaft seal pressure, and whether pumps and valves admit air. Low unit load, low condensate temperature and low ambient temperature make oxygen dissolve into water very easily. Properly increase the sealing water pressure of the condensate pump and adjust the sealing water to trickle evenly onto the condensate pump packing. Check the dissolved oxygen of the chemical makeup water; if it exceeds the limit, contact the chemical department to make adjustments. Causes and Treatment: Deaerator Dissolved Oxygen Exceedance Check whether condensate dissolved oxygen exceeds the limit (same checks as above). Check the opening of the deaerator exhaust-to-atmosphere valve; if too small, open it appropriately. Check whether high-pressure heater drain is normal; a leaking valve can cause oxygen to dissolve into the water. Check whether a large amount of cold water is being supplied to the deaerator — common at low load when boiler slag-cooling water is excessive. Check the deaerator heating steam source; if extraction steam pressure and temperature are low, the water is not heated sufficiently and oxygen is not fully released. Internal structure damage of the deaerator — blocked or fallen nozzles, internal breakage, etc. Large load fluctuation with the deaerator water level too high or too low causes exceedance and incomplete deaeration. Air leaking from the feedwater pump sampling valve — common when the sampling valve is not closed in time during feedwater pump shutdown for maintenance. Summary of Common Causes EquipmentCommon CauseCorrective Action CondenserAir in-leakage, low load / low temperature, uneven sealing waterCheck vacuum and seals, raise sealing water pressure, adjust makeup water DeaeratorSmall atmosphere exhaust opening, low load with low water temperature, leaking drainsOpen exhaust valve, raise heating steam, check drains and internals Feedwater pumpSampling valve admits air after shutdownClose the sampling valve in time Conclusion Condenser and deaerator dissolved oxygen exceedance can lead to unsafe events, so it must be adjusted immediately once detected. In daily operation, the most frequent causes of deaerator dissolved oxygen exceedance are low water temperature at low load, low ambient temperature, uneven adjustment of condenser sealing water, a small deaerator atmosphere exhaust opening, and air admitted through the feedwater pump sampling valve after shutdown. Correctly identifying the cause allows operators to restore dissolved oxygen to within the qualified range quickly and keep the unit running safely.
View More
Latest company case about The Overlooked Accumulator: How a Silent Device Safeguards Turbine Hydraulic and Lube Oil Systems
The Overlooked Accumulator: How a Silent Device Safeguards Turbine Hydraulic and Lube Oil Systems

2026-10-09

The Overlooked Accumulator: How a Silent Device Safeguards Turbine Systems Many operating personnel know only that an accumulator exists. Some cannot even tell where it is installed or what it actually does. So why does this device get overlooked? First, unlike pumps, valves and bearings, the accumulator has no temperature, vibration or current monitoring. Second, it simply “stands quietly” — when system pressure is normal, no one notices it is there. Third, operating procedures rarely describe it clearly, and there is little dedicated training on it. In turbine systems, however, the accumulator plays a critical role. It is mainly installed in the hydraulic control oil system (EH oil / governing oil) and the lube oil system. 1. How the Accumulator Works Inside the accumulator, an inert gas (usually nitrogen) is separated from the hydraulic oil by an elastic diaphragm, bladder or piston. Its energy cycle works in two stages: Energy storage: When system pressure rises, hydraulic oil enters the accumulator and compresses the gas. The gas volume shrinks and its pressure increases, so energy is stored in the form of compressed gas. Energy release: When system pressure drops or a large flow is momentarily required, the gas expands and pushes the hydraulic oil back into the system, supplying flow or holding pressure. This is exactly why, after an oil pump stops, the oil pressure does not drop to zero immediately but declines slowly — the accumulator is at work. During operation, if a pump suddenly fails, the accumulator buys operators precious golden time to respond. 2. Main Roles of the Accumulator FunctionDescriptionBenefit Store pressure oil & emergency supplyWhen a sudden leak or short pump failure occurs, the accumulator quickly releases pressure oil to hold oil pressure briefly, ensuring valves and actuators still act.Buys time for operational response Absorb pressure shocks & buffer pulsationPump start/stop and fast valve switching create pressure fluctuation and water-hammer shocks; the accumulator absorbs them and reduces oil pressure pulsation.Protects pipes and pressure components, cuts vibration Maintain system pressure stabilityWhen small amounts of oil are used and pressure drops slightly, the accumulator releases oil to compensate.Stabilizes working pressure, avoids frequent pump cycling and reduces energy consumption Compensate for leakageMinor internal leakage in hydraulic valves and seals slowly lowers pressure over long runs; the accumulator continuously tops up a small amount of oil.Maintains system pressure over time 3. Operation Monitoring and Inspection Monitor whether the EH oil main pipe pressure and the lube oil main pipe pressure are steady, and check for abnormal fluctuation. Inspect the accumulator appearance: leakage, vibration, abnormal noise, and frosting or oil seepage at the charging valve. Conclusion The accumulator is a quiet but indispensable guardian of turbine hydraulic and lube oil systems. Although it is easy to overlook, it stores energy for emergencies, absorbs pressure shocks, stabilizes system pressure and compensates for leakage. Regular monitoring of oil pressure stability and careful visual inspection of the accumulator are simple steps that can prevent unexpected downtime and protect the entire system.
View More
Latest company case about Vortex Flowmeter Troubleshooting Case Study: Field Diagnosis and Maintenance Solutions for Flow Measurement
Vortex Flowmeter Troubleshooting Case Study: Field Diagnosis and Maintenance Solutions for Flow Measurement

2026-09-14

Project Background Vortex flowmeters are a cornerstone of accurate flow measurement across the chemical, petrochemical, water treatment and power generation industries. However, even a well-engineered vortex flowmeter can deliver unreliable readings when it is exposed to adverse installation conditions, electrical interference or insufficient maintenance. This case study summarizes a structured field-troubleshooting program developed for a manufacturing client whose process control and measurement accuracy had been repeatedly disrupted by recurring vortex flowmeter faults. Key Fault Symptoms and Corrective Actions 1. Pipeline Has Flow, but the Vortex Flowmeter Produces No Output or a Blank Display Power supply not connected or voltage out of the operating range: inspect the power supply and confirm that the voltage matches the meter specification. Flow rate too low and below the meter minimum range: increase the flow rate or reselect a flowmeter with a suitable measuring range. Pipeline valve closed or not fully opened: verify and correct the valve position. Signal amplifier board failure: contact after-sales support to repair or replace the amplifier board. 2. No Flow in the Pipeline, but the Meter Still Outputs a Signal Strong electrical or high-frequency interference near the meter: relocate the installation point away from the interference source. Excessive pipeline vibration or a nearby vibration source: reinforce the pipeline or choose a new mounting location. Valve not fully closed: inspect and ensure the valve closes tightly. Amplification gain or trigger sensitivity set too high: adjust the parameters to appropriate values. 3. Unstable Flow Output Electrical interference combined with poor grounding: check the shielded signal cable and amplifier-board fasteners to guarantee solid grounding. Insufficient straight pipe length or a mismatched pipe bore: reinstall according to the manual and select a matching pipe. Pipeline vibration: reinforce the pipeline or relocate the meter. Non-concentric installation, seal gasket problems or disturbing valves upstream/downstream: reinstall the meter or inspect the valves. Fluid not filling the pipe or a gas–liquid two-phase flow: re-select a proper installation point. Foreign objects or wrappings at the meter inlet: remove the meter and clean the inlet. 4. Displayed Flow Does Not Match the Process Flow No real-time temperature/pressure compensation for gas or steam, or incorrect setpoints: add temperature and pressure elements and verify the actual operating conditions. Incorrect installation positions of the temperature and pressure elements: re-select and reinstall the measurement points. 5. Additional Faults and Remedies Sensor damage caused by mechanical impact, over-temperature, over-pressure or corrosion: replace the sensor promptly. Display failure due to poor contact or damage: reconnect or replace the display. Long-term operation without maintenance: implement a scheduled maintenance and inspection program. Quick-Reference Troubleshooting Summary Symptom Likely Root Cause Recommended Action No output with flow present Power, valve or amplifier board Check power, open valve, repair or replace the amplifier Output present without flow Interference, vibration or high gain Relocate, reinforce the pipe, adjust parameters Unstable output Grounding, straight pipe or two-phase flow Fix grounding, reinstall, clean the inlet Reading mismatch Missing compensation or wrong installation Add T/P elements, verify setpoints Results and Client Benefits By applying this systematic diagnostic checklist, the client maintenance team reduced unplanned flowmeter downtime, restored measurement accuracy and extended the service life of its vortex flowmeters. Routine inspection, periodic cleaning of the sensor and rotor surfaces, and timely replacement of worn components proved to be the most effective measures for preventing faults before they affected production. This case demonstrates that reliable vortex flowmeter performance depends not only on correct product selection but also on proper installation, grounding and a disciplined preventive maintenance schedule.
View More
Latest company case about E+H Mass Flowmeter Compressed Air Parameter Setup Case Study: Configuration Guide for Gas Flow Measurement
E+H Mass Flowmeter Compressed Air Parameter Setup Case Study: Configuration Guide for Gas Flow Measurement

2026-09-14

Project Background Accurate measurement of compressed air is essential for energy management, leak detection and cost control in modern production facilities. When an industrial client deployed an E+H mass flowmeter to monitor compressed air consumption, the initial readings were unstable and occasionally inaccurate because the meter had been left with factory defaults intended for liquid service. This case study documents the complete parameter configuration performed to obtain reliable gas flow measurement. Key Parameters Configured for Compressed Air 1. Measurement Unit Settings The mass flow unit (for example kg/h or t/h) and the totalizer unit were set to match the actual application so that operators could read and record consumption consistently with their energy-management system. 2. Range Settings The lower (4 mA) and upper (20 mA) limits of the analog output were configured according to the expected compressed-air flow range, ensuring that measured values are displayed accurately within the calibrated span. 3. Low Flow Cutoff (Optional) To suppress tiny flows and signal noise, a low flow cutoff of approximately 1%–5% of the full range was applied, preventing minor fluctuations from affecting measurement precision. 4. Empty Pipe Detection (EPD) Because compressed air has a very low density, empty pipe detection was switched off for gas measurement. Leaving EPD enabled can cause false alarms and measurement interruptions when the gas density is low. 5. Flow Direction Setting The measuring direction (forward or reverse) was configured according to the actual installation orientation so that the meter correctly identifies the direction of media flow. 6. Density-Related Parameters (Optional) To calculate standard volumetric flow or perform density compensation, the standard-condition air density (about 1.293 kg/m³) was entered and density compensation was enabled. 7. Damping Settings (Optional) The flow damping factor was tuned to the on-site working conditions to smooth the measurement signal and reduce output fluctuation. Configuration Summary Parameter Recommended Setting Purpose Measurement unit kg/h or t/h + totalizer unit Match application and reporting Range (4–20 mA) Lower and upper limits per expected flow Accurate span display Low flow cutoff 1%–5% of full range Remove noise and micro-flows Empty pipe detection Disabled for gas Avoid false alarms Flow direction Forward or reverse per installation Correct flow recognition Air density 1.293 kg/m³ + compensation Standard volumetric flow Damping Tuned to site conditions Smooth the signal Results and Client Benefits After the parameters were configured through the flowmeter's operating interface and companion commissioning software, the client obtained stable, accurate compressed-air measurements, improved the reliability of its energy-monitoring data and gained a clearer picture of air consumption across production lines. These settings confirm an important practice: the exact procedure may vary slightly between models, so consulting the device manual or an E+H technical support specialist ensures the optimum configuration for each application.
View More
Latest company case about Thermal Power Plant TSI Case: Turbine Mechanical Measurement and Monitoring for Safe Unit Operation
Thermal Power Plant TSI Case: Turbine Mechanical Measurement and Monitoring for Safe Unit Operation

2026-09-08

Customer Background The turbine-generator is the heart of a thermal power plant, and mechanical quantity instruments are the electrocardiogram that watches it beat. In the thermal instrumentation of a 600 MW-class power plant we support, the Turbine Supervisory Instrumentation (TSI) system continuously monitors shaft relative vibration, bearing absolute vibration, axial displacement, differential expansion, casing expansion, rotor eccentricity, speed / zero speed and key phasor. However, frequent false TSI alarms, drifting readings and unclear maintenance standards troubled the instrumentation team, so they worked with our engineers to rebuild a reliable measurement and maintenance system. Challenge Frequent false TSI alarms that disturbed operators and risked unit trips; Unstable or drifting signals on shaft vibration, axial displacement and expansion channels; Gap voltage moving out of the linear zone, signal loss caused by open or short circuits, and inaccurate readings from contamination, loose brackets and aging sensors; No clear standards-based procedure for installation, overhaul and acceptance of mechanical measurement loops. Solution: A Complete Measurement and Maintenance System Our solution covers the six parameter families of turbine mechanical condition monitoring - vibration, displacement, expansion, speed, eccentricity and key phasor - built on three core sensing technologies: Eddy-current sensors - the workhorse of TSI measurement. Non-contact measurement based on the eddy-current effect with a 0-10 kHz frequency range, resolution down to 0.01 mm and strong resistance to oil contamination. Typical output is -4 V to -20 V DC, with the gap voltage set at the linear midpoint (about -10 V DC for a 200 mV/um, 8 mm probe). They cover shaft vibration, axial displacement, differential expansion, eccentricity, key phasor and speed measurement. LVDT sensors - contact-type displacement sensors for large travels up to 0-80 mm with linearity within ±1% F.S., mainly used for casing expansion and part of differential expansion. TD-2 series thermal expansion sensors provide 4-20 mA retransmission plus local indication. Magnetoelectric velocity sensors - the traditional choice for bearing absolute vibration, rigidly mounted on machined bearing pedestals; modern units may use piezoelectric accelerometers with double integration. Typical 600 MW Unit TSI Configuration Monitoring ItemTypical Configuration Shaft vibration7 bearings x X/Y directions, 14 eddy-current probes Bearing absolute vibration7 magnetoelectric velocity sensors Axial displacement2-3 eddy-current probes (redundant) Differential expansion1-2 eddy-current or LVDT probes per HP/LP side Casing expansion1-2 LVDT sensors Eccentricity / key phasor1 eddy-current probe each Speed / zero speed2-3 sensors (magnetoelectric + eddy-current combination) For sensor selection, the probe coil diameter determines the measuring range: 8 mm probes cover about ±1 mm for shaft vibration, eccentricity and key phasor; 11 mm probes ±2 mm; 14 mm probes ±4 mm for medium axial displacement and differential expansion; 25 mm probes ±6 mm; and 50 mm probes ±12 mm for large expansion measurement. Fault Handling and Maintenance Highlights Following GB/T 34578-2017 and DL/T 1056-2019, we helped the plant establish daily inspection and troubleshooting mechanisms for the five most common fault families: unstable output or drift, abnormal gap voltage jumps, signal loss or constant output, inaccurate readings, and frequent false alarms. Key engineering practices include: Single-end grounding of the shielded cable at the TSI cabinet side only, with the probe side floating to eliminate ground loops; Checking probe coil resistance (about 7.5 Ω ± 0.5 Ω for typical series) to identify open or short circuits; Sealing high-frequency joints with heat-shrink tubing and keeping them insulated and floating as required by DL 5190.4-2019; Setting the zero reference with the thrust disc seated against the thrust bearing, and verifying protection set-points by simulated wear tests; Calibrating sensors every 6-12 months, keeping insulation resistance above 1 MΩ, and maintaining complete technical archives. Outcome After the retrofit, false alarms were eliminated, measured values returned to the trustworthy linear zone, and the plant gained a clear standards-based workflow covering installation, routine inspection, overhaul acceptance and protection logic testing (DL/T 1012-2006, GB/T 11348.2-2012, GB/T 6075). Shaft vibration evaluation is now performed against the A/B zones of the national standards, and every measurement loop truly acts as the sentry of long-term, safe turbine operation. For OEM supply of eddy-current probes, preprocessors, LVDT and velocity sensors, or TSI retrofit and commissioning support, contact our engineering team.
View More

GREAT SYSTEM INDUSTRY CO. LTD
MARKET DISTRIBUTION
map map 30% 40% 22% 8%
map
map
map
WHAT CUSTOMERS SAYS
Alexandr Blagov
Hello Qiang. Happy New 2021 Year! We start working Year from today. Thank you very much for cooperation in the last year and hope we will do it better this year!
Hbabaee
Frank, Thank you for your honesty and your company trusty last year I hope will be extend our business together next year.Have a good holiday.
Niloufar Soltani
It has been very nice to cooperate with you through all these years and thank you so much for your kind support and best service!
CONTACT US AT ANY TIME!
sitemap |  Privacy Policy | China Good Quality GE Bently Nevada Supplier. Copyright © 2021-2026 GREAT SYSTEM INDUSTRY CO. LTD . All Rights Reserved.