Generator Gas Replacement During Startup and Shutdown: Full Procedure and Key Safety Precautions
2026-10-09
Generator Gas Replacement During Startup and Shutdown: Full Procedure and Safety Precautions
Generator gas replacement must be carried out only after the generator has passed its air-tightness test and its insulation is qualified. The replacement can be performed while the rotor is stationary or running on the turning gear. This article walks through pre-checks, precautions, the startup and shutdown replacement processes, and routine hydrogen makeup.
1. Pre-Replacement Checks
Put the turbine lube oil system and seal oil system into service.
Carry out a full inspection of the hydrogen system to confirm replacement conditions are met.
Before replacement, stop the circulating fan and isolate the online humidity meter and purity meter.
Tools: power reel, copper wrench, copper hook (never use iron wrenches or hooks), and lamps (for baking piping and valves when using CO2).
2. Key Precautions During Replacement
No hot work is allowed in the surrounding area during gas replacement.
Copper wrenches and hooks must be used — iron tools are forbidden to avoid sparks.
When working around the hydrogen system, the site must be well ventilated and well lit.
Closely watch that the oil-hydrogen differential pressure tracks automatically and correctly; if not, adjust manually.
3. Startup Gas Replacement
Step 1 — Replace air with CO2:
Connect the CO2 cylinder outlet to the manifold interface.
Open the generator CO2 inlet valve.
Slowly open the CO2 discharge valve and let CO2 enter the generator, carefully controlling the charging rate.
Maintain the generator internal gas pressure at 0.02–0.03 MPa during replacement.
Repeatedly purge the dead corners, sampling valves and oil-water detector drains. When CO2 purity reaches ≥ 85%, purity is qualified and CO2 replacement is complete.
Step 2 — Replace CO2 with hydrogen:
Drain the CO2 from the generator.
Contact the hydrogen plant operator and confirm the makeup method.
Maintain the generator internal gas pressure at 0.02–0.03 MPa during replacement.
Control the hydrogen charging rate to prevent a hot spot from excessive hydrogen velocity at pipe reducers, which could cause an accident.
Repeatedly purge the dead corners, sampling valves and oil-water drains. When hydrogen purity reaches ≥ 96%, purity is qualified and hydrogen replacement is complete.
Put the hydrogen dryer, circulating fan, purity meter, humidity meter and generator insulation device into service.
4. Shutdown Gas Replacement
First replace the generator hydrogen with CO2; purity ≥ 95% is qualified.
Then replace the generator CO2 with air; purity reaching 15% is qualified.
The shutdown process is similar to startup — only the required purity differs at each stage.
5. Hydrogen Makeup During Operation
Open the hydrogen makeup valve.
Contact the hydrogen plant for makeup.
Adjust the makeup pressure.
When hydrogen pressure is sufficient, contact the hydrogen plant to stop makeup; after the makeup pressure drops, close the makeup valve.
Control the makeup rate throughout the process.
6. Summary of Key Points
PointRequirement
Online metersIsolate the online purity meter and humidity meter for both startup and shutdown replacement.
SafetyNo hot work at all times; ensure ventilation; use copper tools only.
Differential pressureEnsure oil-hydrogen differential pressure tracks automatically; adjust promptly if not.
Speed controlControl the charging and exhausting speed during replacement.
PurityPurity must always meet the values specified in the operating procedures.
View More
Deaerator Pressure and Temperature Changes: Why They Affect Dissolved Oxygen in Boiler Feedwater Systems
2026-10-09
Deaerator Pressure and Temperature Changes: Why They Affect Dissolved Oxygen
During normal operation of a turbine unit, dissolved oxygen in boiler feedwater always fluctuates whenever the deaerator pressure or temperature rises or falls. But do you really understand how dissolved oxygen changes, and why? This article explains the mechanics behind these fluctuations and how to keep dissolved oxygen within the qualified range.
The Core Principle Behind Deaeration
First, it is essential to understand the core of deaeration: only by heating the water to the saturation temperature that corresponds to the current pressure can the dissolved gases inside the water be released. Pressure and saturation temperature have a one-to-one correspondence. However, the change of water temperature always lags behind the change of pressure, and this lag is the root cause of dissolved oxygen fluctuation in the deaerator.
Case 1: When Deaerator Pressure Suddenly Rises
When the deaerator pressure rises, the water temperature does not rise in sync. At this moment, the water temperature is lower than the saturation temperature at the current pressure. Because the water has not reached its saturation temperature, deaeration performance deteriorates, and the dissolved oxygen in the water rises.
Immediate effect: Water temperature lags below saturation temperature → deaeration weakens → dissolved oxygen increases.
After a period of time: Once the deaerator heats the water up to the saturation temperature at the new pressure, dissolved oxygen falls again and returns to the qualified range.
Case 2: When Deaerator Pressure Suddenly Drops
When the deaerator pressure drops, the water temperature decreases slowly. At this moment, the water temperature is higher than the saturation temperature at the current pressure, so the water is in an “oversaturated” state. In this state, the dissolved gases in the water are more easily released, and the dissolved oxygen decreases.
Immediate effect: Water temperature lags above saturation temperature → gas readily escapes → dissolved oxygen drops temporarily.
After a period of time: Once the water temperature gradually falls and matches the saturation temperature of the new pressure, deaeration capacity returns to normal and dissolved oxygen slowly climbs back.
Summary of Pressure Change Effects on Dissolved Oxygen
Pressure ChangeWater Temperature BehaviorWater StateDissolved Oxygen Trend
Pressure suddenly risesLags below saturation temperatureUnder-saturatedIncreases, then falls back to normal
Pressure suddenly dropsLags above saturation temperatureOversaturatedDecreases temporarily, then climbs back
Conclusion
In short: when deaerator pressure rises sharply, the water temperature lags below the saturation temperature, so dissolved oxygen increases; when pressure drops sharply, the water temperature lags above the saturation temperature, gases are easily released, and dissolved oxygen temporarily decreases. Understanding this lag relationship helps operators anticipate dissolved oxygen fluctuation before it exceeds the qualified range, ensuring stable and reliable deaeration performance in boiler feedwater systems.
View More
How Long Should the Straight Pipe Sections Be Before and After an Electromagnetic Flow Meter?
2026-09-21
When installing an electromagnetic flow meter, one of the most common questions on site is how long the straight pipe sections before and after the meter should be. The flow profile inside the pipe directly affects measurement accuracy, so getting these lengths right matters.
The Basic Rule: 5D Upstream and 2D Downstream
As a starting reference, use an upstream straight section of at least 5D and a downstream section of at least 2D, where D is the nominal pipe diameter. For a DN100 meter, that means keeping at least 500 mm upstream and 200 mm downstream. These values are a practical layout guide, and the actual requirement depends on the fittings installed ahead of the meter.
Why the Upstream Section Must Be Longer
An electromagnetic flow meter calculates flow rate from the induced voltage generated as a conductive liquid passes through a magnetic field. After the liquid passes an elbow, tee, valve, or reducer, the velocity distribution is distorted and may swirl. If the meter is too close to these fittings, the flow has not stabilized when it enters the measuring tube, and the reading is affected. The upstream straight section gives the disturbed flow time to recover. Because the fluid entering the meter comes directly from the upstream side, the upstream section is normally longer than the downstream one.
How Fittings Affect the Required Length
FittingRecommendation
Simple straight pipe (no disturbing fittings nearby)Upstream ≥5D, downstream ≥2D
Single 90° elbowKeep the upstream straight length as long as possible
Two consecutive elbows (especially out of plane)Lengthen the upstream section; swirl is stronger
TeeIncrease the distance to give the flow room to recover
Control valveBest layout: upstream pipe → flow meter → control valve, placing the valve after the meter
Pump outletKeep a full upstream section, ensure the pipe runs full, and avoid air entrainment or cavitation
What Counts as an Effective Straight Pipe Section
A straight pipe section is not just about the pipe being physically straight. Within this length there should be no elbows, tees, valves, obvious reducers, or deeply inserted parts such as temperature sleeves or sampling tubes, and the diameter must stay consistent without sudden changes in cross-section. A pipe that measures 5D but contains a deep thermowell still disturbs the flow, so do not rely on length alone — check what is inside the pipe.
When Space Is Limited
In retrofit projects the piping is already built and space is tight. In that case: check the meter's manual for the specific straight-section requirement; see whether elbows, tees, or valves can be moved; check whether the meter position can be adjusted; and, if space is truly limited, select a model designed for shorter straight sections. Do not judge only by whether the meter physically fits — make sure the measurement conditions are adequate.
Summary
For an electromagnetic flow meter, start with upstream ≥5D and downstream ≥2D. If elbows, tees, control valves, pump outlets, or reducers are present upstream, lengthen the straight sections accordingly, and always confirm the final requirement against the specific model's manual. Check three things: what fittings are ahead of the meter, whether the straight section is truly clean, and what the manual requires.
If you need help selecting the right electromagnetic flow meter or confirming installation requirements, please contact us for professional advice and a tailored quotation.
View More
Why Radar Level Meters Should Not Be Installed Close to the Tank Wall: Causes and Fixes
2026-09-21
Radar level meters are widely used for non-contact level measurement in storage tanks across the chemical, water treatment, oil and gas, and food industries. They are accurate and low maintenance, yet their performance depends on one easily overlooked detail: the installation position. Many on-site problems, such as readings that fluctuate at low levels, sudden value jumps, and false echoes, can be traced back to a radar mounted too close to the tank wall.
Why Installation Position Matters
A radar level meter emits an electromagnetic beam toward the medium surface and calculates the level from the echo time. Because the beam has a beam angle, its coverage widens as the measuring distance increases. The beam radius is approximately r = H × tan(θ/2), where H is the distance from the antenna to the surface and θ is the beam angle. The whole beam path, from the antenna down to the low-level zone, must therefore be considered together.
Reflections from the Tank Wall and Internal Structures
The radar wave is reflected not only by the liquid surface but also by the tank wall, welds, ribs, pipes, and ladders, and metal surfaces reflect strongly. When the radar is too close to the wall, part of the beam hits the wall, so the returned signal contains wall and structure echoes as well as the true liquid echo, appearing as several peaks on the echo curve. With low dielectric media, foam, steam, agitation, or a moving surface, level identification becomes much harder, which is the origin of many so-called "false echoes".
Why Low Levels Are More Unstable
At high level the antenna is close to the surface and the beam is still concentrated. As the level falls, the propagation distance grows and the beam widens; once it reaches the wall, ribs, coils, or other internals, the echo curve changes. This explains why some tanks read steadily at high level but begin to jump below a certain point, with fluctuation increasing as the level drops further. The low-level zone must therefore be included when selecting the mounting point.
Multipath Reflections
Radar waves travel along more than one path inside a tank. Some signals hit the surface directly, while others reflect off the wall or internal structures several times before returning. Because the paths differ in length, they return at different times and produce multiple peaks.
How Far from the Wall Should a Radar Be Mounted?
Values such as 300 mm, 500 mm, or 1 m are often quoted on site, but the correct distance depends on the equipment and the tank. The main factors are:
FactorWhy It Matters
Beam angleA wider beam spreads more as it travels, so a wider clear space is required for the same distance.
Tank heightTaller tanks have a longer measuring distance at low level, so low-level beam coverage must be checked.
Frequency and antenna typeDifferent frequencies and antennas produce very different beam widths; narrow-beam models suit tight spaces.
Internal structuresLadders, agitator shafts, heating coils, feed pipes, and ribs create strong interference echoes.
The cleaner the main beam path, the better the echo and the more stable the reading.
80 GHz Radar for Tight Spaces
80 GHz radar offers a narrower, more focused beam. At the same distance it covers a smaller area, making it easier to avoid walls, coils, and agitators. This is why 80 GHz radar is increasingly chosen for small tanks, vessels with dense internals, and locations with limited space. Aligning the antenna so the beam travels straight down along the tank usually produces a clearer echo.
Other Factors That Affect the Echo
Near the feed inlet: splashing, foam, and turbulence disturb the beam; offsetting the sensor from the inlet improves stability.
Near the agitator: rotating blades create periodic reflections; moving the radar away from the agitation zone gives a cleaner signal.
Ladders, coils, and ribs: these metal parts reflect strongly, so keep the main beam in an open area.
Long nozzles: a nozzle that is too long or narrow causes extra reflections.
Checking Radar Status After Installation
Start with the echo curve: check where the surface echo sits, how strong it is, whether clear interference peaks appear at fixed positions, and which echo the instrument is tracking.
Summary
When installing a radar level meter, leave a relatively clean propagation path for the beam. If the meter is too close to the tank wall, the wall, welds, ribs, and other metal structures enter the beam, and the extra echoes make level identification harder. This article refers mainly to non-contact radar level meters. If you need help selecting the right radar level meter, please contact us for professional advice and a tailored quotation.
View More
Industrial Field Instrument Inspection Guide: What to Check for Reliable Plant Measurement and Safety
2026-09-14
Why Field Instrument Inspection Matters
Field instruments operate for years in harsh environments characterized by vibration, moisture, corrosion and temperature swings. Over time these conditions lead to water ingress, leaks, loose wiring and signal drift. Effective inspection therefore looks far beyond a simple display check and combines the instrument body, piping, cabling, grounding, explosion-proof integrity and the surrounding installation environment.
1. Instrument-by-Instrument Checks
Pressure and Differential-Pressure Gauges
Look for water droplets, mist or moisture inside the case.
Confirm the pointer is not stuck, jumping, bent or detached.
Verify that the dial scale, range, unit and tag number are clear.
Inspect the housing, glass and connections for damage, corrosion or leakage.
Ensure the calibration label is intact and within its validity period.
Transmitters
Applies to pressure, differential-pressure, level, solids-level and temperature transmitters:
Check the housing, terminal compartment and cable entries for water ingress or moisture.
Confirm the displayed value, unit and status information are normal.
Compare the local display with the control-system reading for significant deviation.
Inspect the manifold, impulse connectors and drain ports for leaks.
Ensure mounting brackets, sunshades and fasteners are not loose or corroded.
Valve Positioners and Pneumatic Accessories
Verify the positioner, feedback lever and mounting bracket are secure.
Check the air-supply, output and tubing connections for leakage.
Watch for valve creeping, oscillation, hysteresis or incomplete travel.
Confirm the positioner opening matches the actual valve position.
Inspect the filter regulator, pressure gauge and drain device.
Gas Detectors and Audible/Visual Alarms
Check the enclosure, junction box and mounting bracket for damage or looseness.
Confirm no water, condensation or moisture has entered the device.
Ensure the sensor inlet is not blocked by dust, oil or debris.
Verify status indication and the absence of faults or communication errors.
Confirm calibration, verification and sensor-replacement labels are current.
Temperature Instruments
Ensure the sensing element, transmitter and protective sleeve are secure.
Check that compensating or extension cables do not touch hot surfaces.
Confirm the local reading is reasonable and stable compared with the control system.
Inspect the terminal box, cable and protective tube for water ingress or damage.
2. Piping, Cables and Grounding
Impulse and pressure lines: verify neat routing, reliable supports, and check fittings, ferrules, welds and valves for leaks, vibration, corrosion, cracks or blockages.
Manifolds and drain valves: confirm the manifold position matches the operating condition, and that equalizing, isolation and drain valves are correctly set.
Capillary tubes: keep them free from foot traffic, protected from sharp edges and hot surfaces, and free of kinks or corrosion.
Cables and wiring: check for neat, well-supported runs, aged or cracked jackets, loose or corroded terminals, and proper separation of intrinsically safe, signal and power cables.
Grounding system: verify reliable grounding of instruments, solenoid valves and junction boxes, and confirm shield grounding matches the design intent.
3. Explosion-Proof Integrity and Labeling
Confirm cable glands, plugs and accessories meet the site's explosion-proof requirements and that spare ports are sealed.
Inspect flameproof enclosures for cracks, corrosion or missing fasteners.
Ensure sealing rings, compression devices and threaded connections are complete.
Confirm tag plates, nameplates and calibration labels are complete, clear and consistent with the equipment.
4. Environment and Installation Status
Check for standing water, oil, debris or corrosive contaminants around instruments.
Assess exposure to high temperature, vibration, salt spray, steam or wash-down water.
Confirm instruments, brackets, protection boxes and bases are not loose, corroded or deformed.
Keep maintenance access and operating space clear, and remove temporary supports or makeshift binding.
5. Inspection Records and Recommended Practices
Records should describe the exact location and the observed anomaly rather than simply writing "normal" or "abnormal". Recommended example entries include:
Observation
Recommended Action
Slight mist inside the pressure gauge; reading normal for now
Monitor; plan seal replacement
Moisture traces in the transmitter terminal compartment
Inspect the cable gland and sealing
Minor air leak at the positioner supply fitting
Tighten or replace the fitting
Loose impulse-line support with movement during operation
Re-secure the support
Control-system reading deviates from the local display
Schedule a verification check
Conclusion
Field instrument inspection exists to detect water ingress, leakage, vibration, corrosion, loose wiring and poor installation before they escalate into failures. Inspection scopes should be adapted to the process, instrument type, operating environment and historical fault data, and progressively refined into a checklist tailored to each plant.
View More

