logo
About Us
China GREAT SYSTEM INDUSTRY CO. LTD
About Us
GREAT SYSTEM INDUSTRY CO. LTD
Great System Industry (GSI) is a premier provider of process control instrumentation and industrial automation sensors, headquartered in Hong Kong with operations since 1998. As an ISO-certified manufacturer, distributor, and trading company, GSI delivers high-precision measurement solutions—including pressure, temperature, flow, and level sensors—to over 6,000 customers worldwide. With an export ratio of 80%-90% and annual sales reaching $7-10 million, we serve diverse industries across Europe, ...
Read more
Request A Quote
0+
Annualsales
0
Year
Customers
0%
P.C
0+
Employees
WE PROVIDE
THE BEST SERVICE!
You can contact us in various ways
Contact Us
GREAT SYSTEM INDUSTRY CO. LTD

Quality GE Bently Nevada & E&H Instrument factory

Events
Lastest company news about New Field Guide Covers Eight Common Level Gauge Faults with a Five-Step Diagnostic Method
New Field Guide Covers Eight Common Level Gauge Faults with a Five-Step Diagnostic Method

2026-10-21

October 2026 — Most level instrument failures in process plants are not instrument failures at all. That is the core message of a new field guide published this week by our instrumentation engineering team, which catalogues eight recurring level gauge faults and sets out a five-step diagnostic route that maintenance crews can follow without dismantling the transmitter. The guide draws on field service records from chemical, power, metallurgical and pharmaceutical sites, where level is one of the most heavily instrumented and least forgiving measurements: an overflow, a dry-running pump or an empty reactor can mean lost production, safety incidents or environmental releases. Eight Faults That Cover 95% of Field Cases According to the team, the majority of call-outs fall into a small, repeatable set of symptoms. The guide groups them as follows: SymptomFirst area to checkFastest field action No level displaySupply, loop, terminalsMeasure 24 V, then series-measure loop current Reading offset from actual levelParameters, antenna build-up, medium changeThree-way comparison, then verify range and dielectric constant Jumping readingsInterference, grounding, surface agitationRead the trend curve and check shield grounding False level (empty shows half full)False echoes, foam, antenna coatingRead the echo curve and clean the lens Frozen readingStuck float, blocked impulse line, lost-echo holdConfirm with manual dipping, then check by instrument type Reading pinned at full scaleRange, zero suppression, false targetVerify configured range and echo target Zero driftTemperature drift, diaphragm ageing, build-upZero the instrument on an empty tank Output signal faultLoop, load resistance, output modeMeasure current and verify loop resistance A Five-Step Route: Easy Before Difficult Rather than starting with the instrument, the guide recommends working through five checks in a fixed order. Most faults are located within the first three. Verify the symptom. Compare the local display, the DCS value and a manual dip or sight glass to establish whether the problem is in the instrument or in the process. Check supply and signal. Confirm 24 V, test the 4–20 mA loop for opens and shorts, and inspect terminals for corrosion or looseness. Inspect installation and sensor. Antenna build-up, coated probes and blocked impulse lines account for a large share of all level faults. Review the process. Foam, steam, agitation, density changes and inlet surges can make a healthy instrument report nonsense. Check parameters last. Range, zero, dead zone, medium data and false-echo suppression should only be touched once the first four steps are cleared — and recalibration must follow any change. Technology-Specific Failure Patterns The guide also separates failure behaviour by measuring principle, because the same symptom points to different causes depending on the technology: Radar and guided-wave radar: false echoes, antenna build-up and low dielectric constants. Ultrasonic: foam, steam, surface agitation and mounting angle. Magnetic level gauges: stuck floats, failed flap rotation and demagnetisation. Differential pressure and remote-seal types: blocked or liquid-filled impulse lines, coated diaphragms and incorrect zero elevation. Displacer types: build-up jamming and changes in medium density. Aligned with JJG 971-2019 All verification recommendations in the guide follow JJG 971-2019, the Chinese national verification regulation for level gauges issued by the State Administration for Market Regulation, effective 31 March 2020 and replacing the 2002 edition. The regulation requires initial verification, periodic verification and in-service checks. The guide advises plants to retain verification records, noting that the data supports both measurement reliability and incident traceability. “Roughly 80% of the level faults we attend are caused by medium properties, installation position or parameter settings. Genuine hardware failure is under 20%," the engineering team said. “Following the five-step route typically locates the problem within half an hour." Availability The full field guide, including fault-by-fault diagnostic flows, an echo curve interpretation section and a quick-reference table, is available now. Plant maintenance teams can request a copy or discuss a site audit through our instrumentation service desk.
View More
Lastest company news about Choosing Between DN2 DN40 DN50 and DN65 Promag H 300 Hygienic Flowmeters
Choosing Between DN2 DN40 DN50 and DN65 Promag H 300 Hygienic Flowmeters

2026-10-19

Choosing Between DN2, DN40, DN50 and DN65 in the Promag H 300 Range Four bores of the same series: DN2, DN40, DN50 and DN65, all held in stock. Four sizes of one series now sit in our warehouse: DN2, DN40, DN50 and DN65 Promag H 300 instruments, each configured to a distinct order code. The question we are asked most often is which bore belongs on which line. The short answer is that size follows the flow band, and the flow band follows the duty, not the pipe thread that happens to be available. Duty-based selection BoreOrder codeDuty it is chosen forWhat goes wrong if undersized or oversizedDN2 (1/12 in)5H3B02-AAIBAEAFBAFDCS0BA2Micro-dosing and filling machine feed, a few litres per hourOversized: resolution lost at the bottom of the span, batches trimmed by handDN40 (1-1/2 in)5H3B40-AAIBAEAFBAFDCS0BA2CIP supply and return, product recovery loopsUndersized: cleaning velocity limited by the meter rather than the pumpDN50 (2 in)5H3B50-AAIBAEAFBAFDCS0BA2Batching and main hygienic transferUndersized: batch cycles stretched, pressure consumed by the meterDN65 (2-1/2 in)5H3B65-AAIBAEAFBAFDCS0BA2High-throughput filling, dairy and beverage mainsOversized: poor resolution at low overnight flow Four checks before fixing a bore Minimum and maximum flow: the working band should sit inside the achievable range for that bore, not at its edgesConductivity: 5 microsiemens per centimetre as a rule, about 20 for demineralised waterCleaning regime: temperature and chemical exposure decide whether the PFA liner and the IP69 option are neededStraight run available: about 5 DN upstream and 3 DN downstream, or a vertical riser where space is short What all four share Every size in the range uses the same transmitter platform: 4-20 mA HART, pulse and frequency outputs, up to three I/Os, a backlit display with touch control and WLAN access, and Heartbeat Technology for in-line verification. Measurement error is ±0.5 % of reading ±1 mm/s as standard, with the 0.2 % option available, and all sizes span −20 to +150 degrees Celsius with a PFA liner and 316L electrodes as the standard wetted pair. Standardising a plant on one series The practical benefit of buying four sizes of one family is not the price of any single unit. It is that the parameter set, the spare seals, the grounding rings and the operator training are shared, and a maintenance technician who has commissioned the DN50 can commission the DN2 without a second manual. For projects that need several sizes at once, we can ship them as one consignment and supply the matching connection adapters together. Availability All four order codes are held in stock with a minimum order quantity of one piece, T/T or L/C payment and a 12-month warranty, shipping in three to five working days. Send the line list with medium, temperature and flow band for each point, and we will return a bore recommendation per line before the quotation is issued. Contact our instrumentation team for a bore recommendation and stock confirmation.
View More
Lastest company news about Using the DN40 Promag H 300 Flowmeter to Document CIP and SIP Cleaning Cycles
Using the DN40 Promag H 300 Flowmeter to Document CIP and SIP Cleaning Cycles

2026-10-19

Documenting CIP and SIP Cycles With a DN40 Promag H 300 DN40 (1-1/2 in) build: the working size for CIP supply and return headers. A cleaning cycle is only validated if someone can show what happened during it: flow, temperature and time, cycle after cycle, without gaps. Temperature is usually recorded by the skid. Flow is where the evidence is thinnest, because many plants infer it from pump curves. A DN40 electromagnetic sensor placed on the supply or return header turns that inference into a recorded value. What the instrument contributes to the validation file A continuous 4-20 mA or pulse signal that can be logged by the skid PLC alongside temperature and conductivityMeasured cleaning velocity, which is the parameter most often assumed rather than demonstratedAn in-line verification function (Heartbeat Technology) that produces a record without removing the sensorA factory calibration record delivered with the instrument, traceable to manufacturer standards The DN40 build, order code and environment Order code 5H3B40-AAIBAEAFBAFDCS0BA2 covers the DN40 (1-1/2 inch) sensor with a PFA liner and stainless steel housing. It spans −20 to +150 degrees Celsius, so the same unit handles chilled rinse water at the start of a cycle and hot caustic later in the same shift, with sterilisation at 150 degrees Celsius and 5 bar for up to 60 minutes inside the series envelope. The hygienic housing is rated up to IP69, which matters in a room where washdown hoses are used daily. ParameterValueNominal diameterDN40 (1-1/2 in)Medium temperature–20 to +150 °CSterilisation150 °C at 5 bar, max. 60 minLiner / electrodesPFA / 1.4435 (316L), Alloy C22, tantalum, platinumIngress protectionIP66/67, hygienic housing up to IP69Hygiene basis3-A and EHEDG design, FDA-compliant wetted materials Placement rules that keep the data honest Install the sensor where the pipe runs full in both cleaning directions, ideally in a vertical riser on the return leg, with the transmitter accessible for the operator who signs the record. Avoid mounting immediately downstream of a valve that throttles, because the resulting profile biases the reading. If the circuit is cleaned in reverse flow, confirm that the configuration is set for bidirectional measurement so the totaliser keeps counting during backflush. Availability Stock units ship within three to five working days, with one piece as the minimum order and a 12-month warranty. Audit documentation, material certificates and connection adapters can be supplied together with the instrument. Share your cleaning regime and skid drawing, and we will confirm the size and the connection before the order is placed. Contact our instrumentation team for stock confirmation, datasheets and hygiene documentation.
View More
Lastest company news about DN50 Electromagnetic or Mechanical Meter: What Changes in Hygienic Batching
DN50 Electromagnetic or Mechanical Meter: What Changes in Hygienic Batching

2026-10-19

DN50 Electromagnetic or Mechanical Meter: The Real Differences in Batching DN50 (2 in) Promag H 300: no rotor, no shaft seal, no constriction in the measuring tube. Both instrument types will pass product and produce a number. The difference appears in the second year, when the mechanical meter has worn, the product has changed, and the batch record has to be reconstructed. Below is how the two approaches compare on a typical 2 inch hygienic batching line. CriterionMechanical / turbine meterPromag H 300 DN50Moving partsRotor and bearings in the product pathNone; electromagnetic measurementPressure lossConstriction at the rotor, permanent energy costFull bore, no added restrictionBehaviour with viscous productReading drifts with viscosityIndependent of viscosity, density, pressure, temperatureCleaningRotor housing traps product and slows CIPStraight tube, drains and cleans with the lineWear and recalibrationRecalibration intervals shorten with useNo wear parts; in-line verification availableBatch controlPulse output, needs an external totaliserTotaliser inside the transmitter, up to 3 I/Os What this means on the line The energy argument is easy to underestimate. A restriction of a few tenths of a bar, running three shifts, is paid for continuously by the pump. On a 2 inch line the full-bore design of order code 5H3B50-AAIBAEAFBAFDCS0BA2 removes that cost, and equally removes the dead zone where the rotor housing used to sit, so cleaning chemistry reaches the whole pipe. Where the change is felt first Batch repeatability improves because the zero point no longer shifts after CIPProduct changeovers get shorter: no rotor to flush and no bearing to inspectMaintenance planning simplifies: seals and grounding rings are the only wear items in the loopDiagnostics appear in the control system instead of an operator noticing a slow batch When a mechanical meter still makes sense On clean, low-value, non-hygienic water lines with a stable viscosity and no cleaning cycle, a mechanical device can be the cheaper answer, and we will say so. The crossover point is hygienic duty: food, beverage and life science lines where cleaning validation, product loss and changeover time are part of the cost of ownership. There the electromagnetic sensor is usually the lower-cost option once the first year is over. Technical summary ParameterValueOrder code5H3B50-AAIBAEAFBAFDCS0BA2Nominal diameterDN50 (2 in)Measurement error±0.5 % o.r. ±1 mm/s; 0.2 % optionMedium temperature–20 to +150 °COutputs4-20 mA HART, pulse/frequency, status output The DN50 unit is in stock, minimum order one piece, T/T or L/C, 12-month warranty. Send us the existing meter datasheet and the batch specification, and we will lay the comparison against your actual duty rather than a generic table. Contact our instrumentation team for a side by side selection review.
View More
Lastest company news about Pressure Loss on DN65 Dairy Mains: Why a Full Bore Promag H 300 Pays Back
Pressure Loss on DN65 Dairy Mains: Why a Full Bore Promag H 300 Pays Back

2026-10-19

Pressure Loss on DN65 Dairy Mains: The Case for a Full-Bore Sensor DN65 (2-1/2 in) Promag H 300 feeding a high-speed filling line. When a dairy or beverage main already runs near its hydraulic limit, every component in the line is a tax on throughput. A measuring point that constricts the bore is the most expensive kind, because the loss is permanent: it is paid on every litre, every shift, for the life of the plant. This is the argument for choosing a full-bore electromagnetic sensor on DN65 duty rather than a device with an internal rotor or a reduced measuring section. What a constriction actually costs Restrictions penalise the line twice. First as head loss, which the pump has to make up in energy. Second as a limit on peak filling rate: when a filler calls for a short high-flow burst, a restrictive meter forces either a lower burst rate or a higher pump pressure, and both options show up in operating cost. Order code 5H3B65-AAIBAEAFBAFDCS0BA2 avoids the trade-off because the measuring tube has the same bore as the pipe. Design pointEffect on the lineFull-bore PFA-lined measuring tubeNo added restriction; pump duty unchanged from the bare pipe caseNo moving partsNothing to wear, nothing to block; cleaning velocity is set by the pumpBidirectional, independent of viscosityRecipe changes do not require recalibration or a new K factorSeries span to 600 m³/hHeadroom for filling peaks without changing the instrument Where the payback appears Pump energy on a continuously running main, which is the largest and most predictable savingFilling rate, where a higher permitted burst shortens the fill cycleProduct loss, because a straight tube drains and cleans more completely than a rotor housingDowntime, because verification can be done in line rather than by removing the sensor Sizing the DN65 correctly The bore should be chosen from the flow band, not from the adjacent pipe thread. A DN65 sensor is normally selected where the working flow sits in the upper part of the DN50 range or above it, and where the sustained rate justifies the larger line. Running a DN65 instrument at a fraction of its span wastes resolution; running a DN50 above its span wastes pressure. Our team will run the numbers from your flow band and product data before quoting. Service details The unit is supplied new in original Endress+Hauser packaging with a 12-month warranty, minimum order one piece, T/T or L/C. Seals, grounding rings and connection adapters are available as separate items. Stock normally ships within three to five working days. Contact our instrumentation team for throughput and sizing calculation.
View More
Latest company case about Pressure Transmitter Troubleshooting: Six Field Faults Solved at a Chemical Plant
Pressure Transmitter Troubleshooting: Six Field Faults Solved at a Chemical Plant

2026-10-21

A chlor-alkali plant kept losing production time to a problem that looked like instrument failure but was not. Over two quarters the maintenance team replaced eleven smart transmitters across its reactor and pipeline loops, and the false trips continued. A field audit of 26 transmitters on 4–20 mA / HART loops found only two with genuinely failed electronics — the rest were victims of wiring, impulse lines, grounding and calibration. Project Snapshot IndustryChemical / chlor-alkali production ApplicationReactor and transfer line pressure measurement, 4–20 mA with HART Installed base26 smart pressure transmitters (Rosemount 3051, Yokogawa EJA and E+H Cerabar series) ChallengeRepeat trips, drifting readings, unstable output and intermittent HART communication MethodSix-fault diagnostic model: supply → impulse line → signal transmission → calibration Result80% fewer repeat faults in six months; average diagnosis time cut from 4 hours to 45 minutes The Challenge: Replacing Transmitters Did Not Stop the Trips Pressure transmitters are among the most densely installed instruments in any plant, and every control loop depends on them. At this site the symptoms rotated: a reactor loop would show a dead display, a transfer line would drift two hours into a shift, and a downstream DCS trend would break into a sawtooth pattern that drove the control valve to hunt. The default response was substitution. It worked just long enough to convince everyone the instrument was at fault — three months later the same loop was in alarm again. Following the Signal Chain Instead of Guessing A smart transmitter is a three-stage chain, and a fault always belongs to one of those stages: Measurement end — the diaphragm turns pressure into a weak electrical signal. Electronics unit — amplifies it, performs A/D conversion and hands it to the microprocessor. Output end — restores it as 4–20 mA with HART signalling, so the handheld and the DCS can read configuration and diagnostics. Checking by stage removed the guesswork: instead of dismantling a complete instrument, the team asked which stage the symptom pointed at. Six Fault Categories, Six Diagnostic Orders SymptomFirst suspectField action No display / no outputSupply, wiring, loop resistance, display moduleCheck terminal voltage (≥12 V DC two-wire), polarity and load resistor, then swap the display head before opening the housing Output driftImpulse line, diaphragm, temperature, ageingVent to zero and confirm the return to 4 mA; separate zero drift from span drift before calibrating Output jumpingEMI, shield grounding, loose terminals, vibration, real pulsationShort the loop at the transmitter to isolate interference; single-point shield grounding at the control room side Inaccurate readingImpulse line, installation, zero and span, overdue verificationCompare against a standard gauge at 0%, 50% and 100%; check process connection and pipe stress Output frozenBlocked impulse valve, stuck diaphragm, wrong rangeConfirm the process pressure really changed, then check the valve, impulse line and diaphragm Over-range / HART failureOverpressure, open loop, insufficient HART loadVerify 230–600 Ω loop impedance (250 Ω typical), inspect terminals, check configured range and units What the audit actually found Nine loops had impulse lines with liquid accumulation or partial blockage — the largest single cause of drift. Six loops ran signal cable parallel to VFD power cable with the shield grounded at both ends, producing sawtooth trends. Four transmitters had been re-ranged in the DCS but not in the instrument, creating a constant offset operators learned to mentally correct. Three display heads were faulty; the 4–20 mA output behind them was healthy the whole time. Two units were genuine electronics failures and were replaced. Results After Six Months MetricBeforeAfter Repeat pressure-loop faults per quarter102 Average time to diagnose a fault4 hours45 minutes Unplanned transmitter replacements per year112 Loop verification pass rate (JJG 882-2019)72%96% Three Habits That Kept the Faults Away Drain and inspect impulse lines on a schedule. Liquid accumulation and blockage are the number-one external cause of drift and inaccuracy — no amount of recalibration fixes a blocked line. Put every transmitter on a verification cycle. First installation and periodic checks follow JJG 882-2019, records retained. A 0.05-class unit must hold hysteresis within 0.04% at first verification, 0.05% afterwards. Manage cable routing and grounding. Separate signal cable from power cable and ground the shield at one end only — this removes most jumping-output and HART faults. Conclusion Most pressure transmitter faults are not mysterious. They sit on one link of a simple chain — supply, impulse line, signal transmission, calibration — that has loosened, blocked or drifted. Classify by symptom, troubleshoot along the chain, verify against the standard, and the majority of problems are solved on site without a replacement. Still swapping transmitters to chase repeat alarms? Our instrumentation team can run the same six-fault audit across your loops.
View More
Latest company case about Condenser and Deaerator Dissolved Oxygen Exceedance: Causes, Hazards and Corrective Actions
Condenser and Deaerator Dissolved Oxygen Exceedance: Causes, Hazards and Corrective Actions

2026-10-09

Condenser and Deaerator Dissolved Oxygen Exceedance: Causes and Corrective Actions Dissolved oxygen refers to the oxygen dissolved in water, measured in µg/L. During operation, if the oxygen content in condensate or feedwater exceeds the value specified in the operating procedures, it is considered dissolved oxygen exceedance. The dissolved oxygen in the condenser and deaerator must be kept within limits; once it exceeds them, adjustment should be made immediately. Hazards of Dissolved Oxygen Exceedance Oxygen causes oxidation corrosion of metal equipment such as pipes, valves, feedwater pumps, high- and low-pressure heaters, economizers and water walls, producing rust and impurities. Impurities clog filters and valves, affecting feedwater flow. Impurities deposit on heating surfaces, causing scaling, reducing heat-exchange efficiency and potentially leading to tube-wall bursting. Consumption of deoxygenation chemicals increases, raising unit operating costs. Long-term exceedance seriously threatens the safe and stable operation of the unit. Causes and Treatment: Condenser Dissolved Oxygen Exceedance Check whether outside air leaks into the condenser — inspect condenser vacuum, shaft seal pressure, and whether pumps and valves admit air. Low unit load, low condensate temperature and low ambient temperature make oxygen dissolve into water very easily. Properly increase the sealing water pressure of the condensate pump and adjust the sealing water to trickle evenly onto the condensate pump packing. Check the dissolved oxygen of the chemical makeup water; if it exceeds the limit, contact the chemical department to make adjustments. Causes and Treatment: Deaerator Dissolved Oxygen Exceedance Check whether condensate dissolved oxygen exceeds the limit (same checks as above). Check the opening of the deaerator exhaust-to-atmosphere valve; if too small, open it appropriately. Check whether high-pressure heater drain is normal; a leaking valve can cause oxygen to dissolve into the water. Check whether a large amount of cold water is being supplied to the deaerator — common at low load when boiler slag-cooling water is excessive. Check the deaerator heating steam source; if extraction steam pressure and temperature are low, the water is not heated sufficiently and oxygen is not fully released. Internal structure damage of the deaerator — blocked or fallen nozzles, internal breakage, etc. Large load fluctuation with the deaerator water level too high or too low causes exceedance and incomplete deaeration. Air leaking from the feedwater pump sampling valve — common when the sampling valve is not closed in time during feedwater pump shutdown for maintenance. Summary of Common Causes EquipmentCommon CauseCorrective Action CondenserAir in-leakage, low load / low temperature, uneven sealing waterCheck vacuum and seals, raise sealing water pressure, adjust makeup water DeaeratorSmall atmosphere exhaust opening, low load with low water temperature, leaking drainsOpen exhaust valve, raise heating steam, check drains and internals Feedwater pumpSampling valve admits air after shutdownClose the sampling valve in time Conclusion Condenser and deaerator dissolved oxygen exceedance can lead to unsafe events, so it must be adjusted immediately once detected. In daily operation, the most frequent causes of deaerator dissolved oxygen exceedance are low water temperature at low load, low ambient temperature, uneven adjustment of condenser sealing water, a small deaerator atmosphere exhaust opening, and air admitted through the feedwater pump sampling valve after shutdown. Correctly identifying the cause allows operators to restore dissolved oxygen to within the qualified range quickly and keep the unit running safely.
View More
Latest company case about The Overlooked Accumulator: How a Silent Device Safeguards Turbine Hydraulic and Lube Oil Systems
The Overlooked Accumulator: How a Silent Device Safeguards Turbine Hydraulic and Lube Oil Systems

2026-10-09

The Overlooked Accumulator: How a Silent Device Safeguards Turbine Systems Many operating personnel know only that an accumulator exists. Some cannot even tell where it is installed or what it actually does. So why does this device get overlooked? First, unlike pumps, valves and bearings, the accumulator has no temperature, vibration or current monitoring. Second, it simply “stands quietly” — when system pressure is normal, no one notices it is there. Third, operating procedures rarely describe it clearly, and there is little dedicated training on it. In turbine systems, however, the accumulator plays a critical role. It is mainly installed in the hydraulic control oil system (EH oil / governing oil) and the lube oil system. 1. How the Accumulator Works Inside the accumulator, an inert gas (usually nitrogen) is separated from the hydraulic oil by an elastic diaphragm, bladder or piston. Its energy cycle works in two stages: Energy storage: When system pressure rises, hydraulic oil enters the accumulator and compresses the gas. The gas volume shrinks and its pressure increases, so energy is stored in the form of compressed gas. Energy release: When system pressure drops or a large flow is momentarily required, the gas expands and pushes the hydraulic oil back into the system, supplying flow or holding pressure. This is exactly why, after an oil pump stops, the oil pressure does not drop to zero immediately but declines slowly — the accumulator is at work. During operation, if a pump suddenly fails, the accumulator buys operators precious golden time to respond. 2. Main Roles of the Accumulator FunctionDescriptionBenefit Store pressure oil & emergency supplyWhen a sudden leak or short pump failure occurs, the accumulator quickly releases pressure oil to hold oil pressure briefly, ensuring valves and actuators still act.Buys time for operational response Absorb pressure shocks & buffer pulsationPump start/stop and fast valve switching create pressure fluctuation and water-hammer shocks; the accumulator absorbs them and reduces oil pressure pulsation.Protects pipes and pressure components, cuts vibration Maintain system pressure stabilityWhen small amounts of oil are used and pressure drops slightly, the accumulator releases oil to compensate.Stabilizes working pressure, avoids frequent pump cycling and reduces energy consumption Compensate for leakageMinor internal leakage in hydraulic valves and seals slowly lowers pressure over long runs; the accumulator continuously tops up a small amount of oil.Maintains system pressure over time 3. Operation Monitoring and Inspection Monitor whether the EH oil main pipe pressure and the lube oil main pipe pressure are steady, and check for abnormal fluctuation. Inspect the accumulator appearance: leakage, vibration, abnormal noise, and frosting or oil seepage at the charging valve. Conclusion The accumulator is a quiet but indispensable guardian of turbine hydraulic and lube oil systems. Although it is easy to overlook, it stores energy for emergencies, absorbs pressure shocks, stabilizes system pressure and compensates for leakage. Regular monitoring of oil pressure stability and careful visual inspection of the accumulator are simple steps that can prevent unexpected downtime and protect the entire system.
View More
Latest company case about Vortex Flowmeter Troubleshooting Case Study: Field Diagnosis and Maintenance Solutions for Flow Measurement
Vortex Flowmeter Troubleshooting Case Study: Field Diagnosis and Maintenance Solutions for Flow Measurement

2026-09-14

Project Background Vortex flowmeters are a cornerstone of accurate flow measurement across the chemical, petrochemical, water treatment and power generation industries. However, even a well-engineered vortex flowmeter can deliver unreliable readings when it is exposed to adverse installation conditions, electrical interference or insufficient maintenance. This case study summarizes a structured field-troubleshooting program developed for a manufacturing client whose process control and measurement accuracy had been repeatedly disrupted by recurring vortex flowmeter faults. Key Fault Symptoms and Corrective Actions 1. Pipeline Has Flow, but the Vortex Flowmeter Produces No Output or a Blank Display Power supply not connected or voltage out of the operating range: inspect the power supply and confirm that the voltage matches the meter specification. Flow rate too low and below the meter minimum range: increase the flow rate or reselect a flowmeter with a suitable measuring range. Pipeline valve closed or not fully opened: verify and correct the valve position. Signal amplifier board failure: contact after-sales support to repair or replace the amplifier board. 2. No Flow in the Pipeline, but the Meter Still Outputs a Signal Strong electrical or high-frequency interference near the meter: relocate the installation point away from the interference source. Excessive pipeline vibration or a nearby vibration source: reinforce the pipeline or choose a new mounting location. Valve not fully closed: inspect and ensure the valve closes tightly. Amplification gain or trigger sensitivity set too high: adjust the parameters to appropriate values. 3. Unstable Flow Output Electrical interference combined with poor grounding: check the shielded signal cable and amplifier-board fasteners to guarantee solid grounding. Insufficient straight pipe length or a mismatched pipe bore: reinstall according to the manual and select a matching pipe. Pipeline vibration: reinforce the pipeline or relocate the meter. Non-concentric installation, seal gasket problems or disturbing valves upstream/downstream: reinstall the meter or inspect the valves. Fluid not filling the pipe or a gas–liquid two-phase flow: re-select a proper installation point. Foreign objects or wrappings at the meter inlet: remove the meter and clean the inlet. 4. Displayed Flow Does Not Match the Process Flow No real-time temperature/pressure compensation for gas or steam, or incorrect setpoints: add temperature and pressure elements and verify the actual operating conditions. Incorrect installation positions of the temperature and pressure elements: re-select and reinstall the measurement points. 5. Additional Faults and Remedies Sensor damage caused by mechanical impact, over-temperature, over-pressure or corrosion: replace the sensor promptly. Display failure due to poor contact or damage: reconnect or replace the display. Long-term operation without maintenance: implement a scheduled maintenance and inspection program. Quick-Reference Troubleshooting Summary Symptom Likely Root Cause Recommended Action No output with flow present Power, valve or amplifier board Check power, open valve, repair or replace the amplifier Output present without flow Interference, vibration or high gain Relocate, reinforce the pipe, adjust parameters Unstable output Grounding, straight pipe or two-phase flow Fix grounding, reinstall, clean the inlet Reading mismatch Missing compensation or wrong installation Add T/P elements, verify setpoints Results and Client Benefits By applying this systematic diagnostic checklist, the client maintenance team reduced unplanned flowmeter downtime, restored measurement accuracy and extended the service life of its vortex flowmeters. Routine inspection, periodic cleaning of the sensor and rotor surfaces, and timely replacement of worn components proved to be the most effective measures for preventing faults before they affected production. This case demonstrates that reliable vortex flowmeter performance depends not only on correct product selection but also on proper installation, grounding and a disciplined preventive maintenance schedule.
View More
Latest company case about E+H Mass Flowmeter Compressed Air Parameter Setup Case Study: Configuration Guide for Gas Flow Measurement
E+H Mass Flowmeter Compressed Air Parameter Setup Case Study: Configuration Guide for Gas Flow Measurement

2026-09-14

Project Background Accurate measurement of compressed air is essential for energy management, leak detection and cost control in modern production facilities. When an industrial client deployed an E+H mass flowmeter to monitor compressed air consumption, the initial readings were unstable and occasionally inaccurate because the meter had been left with factory defaults intended for liquid service. This case study documents the complete parameter configuration performed to obtain reliable gas flow measurement. Key Parameters Configured for Compressed Air 1. Measurement Unit Settings The mass flow unit (for example kg/h or t/h) and the totalizer unit were set to match the actual application so that operators could read and record consumption consistently with their energy-management system. 2. Range Settings The lower (4 mA) and upper (20 mA) limits of the analog output were configured according to the expected compressed-air flow range, ensuring that measured values are displayed accurately within the calibrated span. 3. Low Flow Cutoff (Optional) To suppress tiny flows and signal noise, a low flow cutoff of approximately 1%–5% of the full range was applied, preventing minor fluctuations from affecting measurement precision. 4. Empty Pipe Detection (EPD) Because compressed air has a very low density, empty pipe detection was switched off for gas measurement. Leaving EPD enabled can cause false alarms and measurement interruptions when the gas density is low. 5. Flow Direction Setting The measuring direction (forward or reverse) was configured according to the actual installation orientation so that the meter correctly identifies the direction of media flow. 6. Density-Related Parameters (Optional) To calculate standard volumetric flow or perform density compensation, the standard-condition air density (about 1.293 kg/m³) was entered and density compensation was enabled. 7. Damping Settings (Optional) The flow damping factor was tuned to the on-site working conditions to smooth the measurement signal and reduce output fluctuation. Configuration Summary Parameter Recommended Setting Purpose Measurement unit kg/h or t/h + totalizer unit Match application and reporting Range (4–20 mA) Lower and upper limits per expected flow Accurate span display Low flow cutoff 1%–5% of full range Remove noise and micro-flows Empty pipe detection Disabled for gas Avoid false alarms Flow direction Forward or reverse per installation Correct flow recognition Air density 1.293 kg/m³ + compensation Standard volumetric flow Damping Tuned to site conditions Smooth the signal Results and Client Benefits After the parameters were configured through the flowmeter's operating interface and companion commissioning software, the client obtained stable, accurate compressed-air measurements, improved the reliability of its energy-monitoring data and gained a clearer picture of air consumption across production lines. These settings confirm an important practice: the exact procedure may vary slightly between models, so consulting the device manual or an E+H technical support specialist ensures the optimum configuration for each application.
View More

GREAT SYSTEM INDUSTRY CO. LTD
MARKET DISTRIBUTION
map map 30% 40% 22% 8%
map
map
map
WHAT CUSTOMERS SAYS
Alexandr Blagov
Hello Qiang. Happy New 2021 Year! We start working Year from today. Thank you very much for cooperation in the last year and hope we will do it better this year!
Hbabaee
Frank, Thank you for your honesty and your company trusty last year I hope will be extend our business together next year.Have a good holiday.
Niloufar Soltani
It has been very nice to cooperate with you through all these years and thank you so much for your kind support and best service!
CONTACT US AT ANY TIME!
sitemap |  Privacy Policy | China Good Quality GE Bently Nevada Supplier. Copyright © 2021-2026 GREAT SYSTEM INDUSTRY CO. LTD . All Rights Reserved.