Send Message
Great System International Limited

Great System International Limited

Home ProductsPEPPERL FUCHS Safety Barrier

PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input

Certification
China Great System International Limited certification
Hello Qiang. Happy New 2021 Year! We start working Year from today. Thank you very much for cooperation in the last year and hope we will do it better this year!

—— Alexandr Blagov

Frank, Thank you for your honesty and your company trusty last year I hope will be extend our business together next year.Have a good holiday.

—— Hbabaee

It has been very nice to cooperate with you through all these years and thank you so much for your kind support and best service!

—— Niloufar Soltani

I'm Online Chat Now

PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input

PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input
PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input

Large Image :  PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input

Product Details:
Place of Origin: Singapore
Brand Name: Pepperl+Fuchs
Model Number: KFD2-UT2-1
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: Negotiable
Packaging Details: carton
Delivery Time: on request
Payment Terms: T/T
Supply Ability: 100+pc+on stock
Detailed Product Description
Manufacture: Pepperl+Fuchs Model Type: Universal Temperature Converter
Country Of Origin: Singapore Signal Type: Analog Input
Safety Integrity Level: SIL 2 Rated Voltage: 20 ... 30 V DC
Power Dissipation: ≤ 0.98 W Shipping Weight: 1 Kg
High Light:

PEPPERL FUCHS Universal Temperature Converter

,

KFD2-UT2-1 Universal Temperature Converter

,

30VDC Pepperl Fuchs Frequency Converter

 

Quick Detail of Universal Temperature Converter

Manufacturer : Pepperl+Fuchs
Product No : KFD2-UT2-1-1
Product Type : Universal Temperature Converter
1-channel signal conditioner
24 V DC supply (Power Rail)
Thermocouple, RTD, potentiometer or voltage input
Voltage output 0/1 V ... 5 V
Configurable by PACTware
Line fault (LFD) and sensor burnout detection
Up to SIL2 acc. to IEC 61508/IEC 61511
Shipping Weight:1kg

Description of Universal Temperature Converter

This signal conditioner is designed to connect RTDs, thermocouples, or potentiometers, and provide a proportional 0/4 mA ... 20 mA signal. The barrier offers 3-port isolation between input, output, and power supply. A removable terminal block K-CJC-** is available for thermocouples when internal cold junction compensation is desired. A fault is indicated by a red flashing LED per NAMUR NE44 and user-configured fault outputs.

 

Specification of Universal Temperature Converter

General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 14+, 15- or power feed module/Power Rail
Rated voltage 20 ... 30 V DC
Ripple within the supply tolerance
Power dissipation ≤ 0.8 W
Power consumption max. 0.8 W
Interface
Programming interface programming socket
Input
Connection side field side
Connection terminals 1, 2, 3; 4, 5, 6
RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
  Measuring current approx. 200 µA with RTD
  Types of measuring 2-, 3-wire connection
  Lead resistance max. 50 Ω per line
  Measurement loop monitoring sensor breakage, sensor short-circuit
Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
  Cold junction compensation external and internal
  Measurement loop monitoring sensor breakage
Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
Voltage selectable within the range -100 ... 100 mV
Input resistance ≥ 1 MΩ (-100 ... 100 mV)
Output
Connection side control side
Voltage output 0 ... 5 V or 1 ... 5 V ; output resistance: ≤ 5 Ω ; load: ≥ 10 kΩ
Connection output I: terminals 7-, 8+
output II: terminals 10-, 11+
Fault signal downscale 0 V or 0.5 V, upscale 5.375 V
Transfer characteristics
Deviation  
  After calibration Pt100: ± (0.06 % of measurement value in K + 0.1 K (4-wire connection))
thermocouple: ± (0.05 % of measurement value in °C + 1 K (1.2 K for types R and S)) , includes ± 0.8 K fault of the cold junction compensation (CJC)
mV: ± 50 µV
potentiometer: ± 0.05 % of full scale, (excludes faults due to lead resistance)
output: 1 to 5 V output: ± 4 mV from 0 to 103.1 % of span; 0 to 5 V output: ± 4 mV from 0.3 to 102.5 % of span
  Influence of ambient temperature Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*)
thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*)), influence of cold junction compensation (CJC) included
mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*)
potentiometer: ± 0.006 % of span/K ΔTamb*)
*) ΔTamb = ambient temperature change referenced to 23 °C (296 K)
  Influence of supply voltage < 0.01 % of span
Reaction time worst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Galvanic isolation
Input/Other circuits basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff
Output/supply, programming input functional insulation, rated insulation voltage 50 V AC
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided.
Indicators/settings
Display elements LEDs
Configuration via PACTware
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 130 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

 

 

Features Of Universal Temperature Converter

  1. 1-channel signal conditioner
  2. 24 V DC supply (Power Rail)
  3. TC, RTD, potentiometer or voltage input
  4. Current output 0/4 mA ... 20 mA
  5. Sink or source mode
  6. Configurable by PACTware] TM
  7. Line fault (LFD) and sensor burnout detection
  8. Up to SIL2 acc. to IEC 61508

 

PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input 0PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Analog Input 1

 

Frequently Asked Questions

Q: Does your goods are new and original?

A: Yes, they are new and original.

 

Q: How long warranty?

A: One-year warranty.

 

Q: Does any certificates can be provided?

A: Yes, it depends on what product you request, please check details with our sales.

 

 

Advantage of Our Team

  • Best possible prices and delivery time
  • Long time experience in the field
  • Well trained staff
  • Own warehouse facilities
  • Best relationships with branch office of manufacture
  • Flexible and individual service for you
  • Cheap and safe forwarder for shipments (air)

 

Contact Details
Great System International Limited

Contact Person: Mrs. Joanna Yang

Tel: +86-13828861501

Fax: 86-755-26850713

Send your inquiry directly to us (0 / 3000)