Product Details:
Payment & Shipping Terms:
|
Manufacturer: | Pepperl+Fuchs | Product Type: | Current/Voltage Driver |
---|---|---|---|
Product No: | KFD2-CD-EX1.32 | Accuracy: | 0.1 % |
Mass: | Approx. 100 G | Voltage: | 25.2 V DC |
Leading Time: | Negotiable | Shipping Weight: | 1 Kg |
High Light: | Isolated Barrier KFD2-CD-EX1.32,1.2 W Pepperl Fuchs Intrinsic Safety Barriers,24 V DC 1 Channel Isolated Barrier |
Manufacturer : Pepperl+Fuchs
Product No. : KFD2-CD-Ex1.32
Product type : 1-Channel Current/Voltage Driver
Power supply : Power Rail or terminals 7+, 8-
Nominal voltage : 20-35 VDC
Rated current : = 50 mA (current output version) = 20 mA (voltage output version)
Input (not intrinsically safe) : Terminals 9+, 10-, 11+
Transmission range : 0-20 mA (current output version) 0-10 V (voltage output version)
Output (intrinsically safe): Terminals 1+, 2-
Transmission range : 0-20 mA (current output version) 0-10 V (voltage output version)
Calibrated accuracy : = 0.1 % incl. non-linearity and hysteresis at 20°C
Dimensions : 4.21" x 0.79" x 4.53" (10.7 x 2 x 11.5 cm)
Weight : 0.1 Kg
Shipping weight : 1 Kg
This isolated barrier is used for intrinsic safety applications. It drives a voltage or current signal from the safe area to I/P converters, electrical valves and positioners located in the hazardous areas. This barrier is designed to provide various inputs and outputs of voltage and current.
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 7+, 8- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Rated current | current output: ≤ 50 mA ; voltage output: ≤ 20 mA | |
Power dissipation | 1.2 W | |
Input | ||
Connection side | control side | |
Connection | terminals 9+, 10-, 11+ | |
Voltage drop | optional current input: approx. 4 V at 20 mA | |
Input current | ≤ 100 µA up to 50 °C (122 °F) at 10 V | |
Limit | optional current input: Input current: approx. ≤40 mA optional voltage input: input voltage: 12 V DC |
|
Transmission range | optional current input: 0 ... 20 mA/optional voltage input: 0 ... 10 V | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Voltage | optional current output: 17 V at 20 mA/optional voltage output: 0 ... 10 V | |
Current | optional current output: 0 ... 20 mA/optional voltage output: ≤ 20 mA | |
Load | optional current output: max. 850 Ω optional voltage output: output resistance max. 3 Ω |
|
Transfer characteristics | ||
Accuracy | 0.1 % | |
Deviation | ||
After calibration | ≤ ± 0.1 % incl. non-linearity and hysteresis at 20 °C (68 °F) | |
Influence of ambient temperature | ≤ ± 0.01 %/K | |
Rise time | < 10 ms | |
Galvanic isolation | ||
Input/power supply | functional insulation, rated insulation voltage 50 V AC | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | UL 61010-1:2004 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BAS 02 ATEX 7203 X | |
Marking | ![]() ![]() ![]() |
|
Voltage | 25.2 V DC | |
Current | optional current output: 93 mA optional voltage output: 95 mA |
|
Power | optional current output: 0.586 W optional voltage output: 0.59 W |
|
Supply | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Input | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | ![]() |
|
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx BAS 05.0041 | |
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
·1-channel isolated barrier
·24 V DC supply (Power Rail)
·Current and voltage input
·Current or voltage output
·Factory configured input/output
·Accuracy 0.1 %
·Up to SIL 2 acc. to IEC/EN 61508
Best possible prices and delivery time
Long time experience in the field
Well trained staff
Own warehouse facilities
Best relationships with branch office of manufacture
Flexible and individual service for you
Cheap and safe forwarder for shipments (air)
Q: Does your goods are new and original?
A: Yes, they are new and original.
Q: How long warranty?
A: One-year warranty.
Q: Does any certificates can be provided?
A: Yes, it depends on what product you request, please check details with us.
Contact Person: Mrs. Joanna Yang
Tel: +86-13828861501
Fax: 86-755-26850713